REPLACING THE BATTERY
WARNING!
This Uninterruptible Power Supply contains potentially haz-
ardous voltages. Do not attempt to disassemble the UPS be-
yond the battery replacement procedure. This UPS contains
no user serviceable parts. Repairs and Battery replacement
must be performed by
QUALIFIED SERVICE PERSONNEL
ONLY.
Do not open or mutilate batteries. Released electrolyte is harmful
to the skin and eyes and may be toxic.
CAUTIONS:
(QUALIFIED
SERVICE PERSONNEL ONLY)
Do not dispose of batteries in a fire. The batteries may ex-
plode. The batteries in this UPS are recyclable. Dispose of
the batteries properly. The batteries contain lead and pose a
hazard to the environment and human health if not disposed of
properly. Refer to local codes for proper disposal requirements
or return the battery to the supplier.
The battery system can present a risk of electrical shock. These batteries
produce sufficient current to burn wire or tools very rapidly, producing molten
metal. Observe these precautions when replacing the batteries:
1. Remove watches, rings, or other metal objects.
2. Use hand tools with insulated handles.
3. Wear protective eye gear (goggles), rubber gloves and boots.
4. Do not lay tools or other metal parts on top of batteries.
5. Disconnect the charging source prior to connecting or disconnecting the
battery terminals.
6. Determine if the battery is inadvertently grounded. If the battery is, remove
the source of the grounding. Contact with any part of a grounded battery
can result in an electrical shock. The likelihood of such shock will be re-
duced if such grounds are removed during installation and maintenance.
This UPS has an easy to replace hot-swappable batteries. Please read all of
the
WARNINGS
and
CAUTIONS
before attempting to service the batteries.
Typical battery life is 3 to 5 years. Environmental factors do affect battery life.
High temperatures, poor utility power, and frequent, short duration discharges
have a negative impact on battery life.
NOTE:
If there is a power interruption
while replacing the hot-swappable batteries, with the UPS on, the load will not
be backed up.
BATTERY REPLACEMENT PROCEDURE
PLEASE READ THE CAUTIONS AND WARNINGS BEFORE ATTEMPTING
TO REPLACE THE BATTERY MODULE
Hot-swappable batteries mean that the battery modules can be replaced with-
out powering down the whole UPS system.
NOTE:
If there is a power interruption while replacing the hot-swappable bat-
tery module, with the UPS on, the load will not be backed up. To hot-swap the
battery module start with step number 6.
1. Turn off the equipment that is plugged into the output receptacles of the
UPS.
2. Press and release the On/Off/Test button on the front panel to turn the UPS
OFF.
NOTE:
Turn the input circuit breaker off for the 208V models.
3. Unplug the UPS's AC power cord from the AC wall outlet.
4. Unplug the equipment from the output receptacles of the UPS.
5. Unplug the computer interface cable from the rear panel of the UPS.
6. Remove the front panel retaining screws. (FIG. 2)
7. Lay the front panel on top of the UPS.
8. Remove the two retaining screws for the battery retaining bracket. (FIG. 3)
9. Remove the battery retaining bracket. (FIG. 3)
10. Disconnect the Battery connectors (red and black). (FIG. 4)
11. Grasp the battery pull tab and gently pull the battery module out of the UPS
and set on the floor. (FIG. 4)
NOTE:
Use Caution, the battery module is heavy.
12. Slide the new battery module into the UPS.
13. Verify proper polarity. Reconnect the battery connectors (red and black).
NOTE:
Some sparking may occur this is normal.
14. Re-install the battery retaining bracket.
15. Re-install the two retaining screws for the battery retaining bracket.
16. Re-install the front panel on the UPS.
17. Re-install the front panel retaining screws.
E750RTXL2U
E1000RTXL2U
E2000RTXL2U
Internal
Battery
Module
Part #
BM0029
BM0031
E3000RTXL2U
E3000RTXLT2U
BM0032
Model #
Replace batteries with the same number and type as originally
installed in the UPS. These batteries have pressure operated vents.
These UPSs contain sealed non-spillable maintenance-free lead
acid batteries.
CAUTION:
E1500RTXL2U
E1500RTXLT2U
BM0030