background image

7

6

The AC normal icon illuminates when the UPS is on and operating in
the AC normal mode.  The AC normal icon will extinguish when oper-
ating in the Battery mode.  The AC normal icon will blink when the
UPS is operating in the Boost and/or the Buck mode.

The On-Battery icon illuminates when the UPS is operating in the
Battery mode.  The On-Battery icon will extinguish when operating in
the  AC normal, Boost and Buck modes.

The Weak/Bad Battery icon illuminates when the UPS detects a
weak battery, bad battery or if the battery is disconnected.  The Weak/
Bad Battery icon is extinguished when the battery's condition is good.

The Fault icon illuminates when the UPS detects an internal fault.
The Fault icon is extinguished when the UPS is operating properly.

The Site Wiring icon (120V models) illuminates when the UPS de-
tects a site wiring problem.  The SWF icon is extinguished when  the
UPS is connected to proper site wiring.

The Load Level Bar Graph operates as follows:
LED #1: When the attached load is >20% the LED will illuminate.
LED #2: When the attached load is >40% the LED will illuminate.
LED #3: When the attached load is >60% the LED will illuminate.
LED #4: When the attached load is >80% the LED will illuminate.
LED #5: When the attached load is >100% the LED will illuminate.

When the amount of load attached to the UPS exceeds 110% of its
power rating; the Overload icon will flash Off and On, all of the LEDs
in the Load Level Bar Graph will be illuminated and the UPS will
sound a constant alarm to indicate that there is an Overload condi-
tion.

The Battery Capacity Bar Graph operates as follows:
LED #1: When the battery capacity is >20% the LED will illuminate.
LED #2: When the battery capacity is >40% the LED will illuminate.
LED #3: When the battery capacity is >60% the LED will illuminate.
LED #4: When the battery capacity is >80% the LED will illuminate.
LED #5: When the battery capacity is >100% the LED will illumi-
nate.

The Multi-Function On/Off/Test Button functions as follows:
When the UPS is Off, press and release the On/Off/Test button after
one beep to turn the UPS On.  

NOTE:

  The input circuit breaker

MUST be on for the 208V models.

When the UPS is On, press and release the On/Off/Test Button after
one beep to turn the UPS Off.

When the UPS is in the Normal AC mode, press and hold the On/
Off/Test button for four beeps, then release the button.  The UPS will
perform a 10-second Self Test.

When the unit is operating in Battery mode, pressing the Alarm Si-
lencer Button will silence the audible alarm.  Once the UPS reaches
the LBW (Low Battery Warning) threshold the alarm will be re-acti-
vated.  The alarm cannot be silenced during the LBW alarm.  Once
the UPS transfers to the AC mode the alarm will be reset to default.

The Scroll Button allows the user to scroll through the UPS param-
eters that are available on the LCD screen.

CONTROL PANEL

NOTE:  

The LCD backlight will illuminate for 1-minute when the UPS switches to the

Battery mode.  When the UPS has an event and/or an error code the LCD backlight
will turn on and remain on to alert the user that an event has occurred.

Summary of Contents for Enterprise Plus LCD RTXL UPS Series

Page 1: ...r s Manual Enterprise Plus LCD RTXL UPS Series Para Systems Inc 1455 Lemay Dr Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com PN 34000431...

Page 2: ...s and Indicators 6 3 Installation 9 4 Operation 15 5 Troubleshooting 19 6 Replacing the Battery 20 7 Obtaining Service 23 8 Specifications 24 9 Configurable Parameters Settings 26 10 Limited Product W...

Page 3: ...ouble free service Please read this manual before installing your Enterprise Plus Series UPS models E750RTXL2U E1000RTXL2U E1500RTXL2U E1500RTXLT2U E2000RTXL2U E3000RTXL2U E3000RTXLT2U as it provides...

Page 4: ...ce in a residential installation This equip ment generates and uses radio frequency and if not installed and used properly that is in strict accordance with the manufacturer s instructions this equip...

Page 5: ...l be illuminated and the UPS will sound a constant alarm to indicate that there is an Overload condi tion The Battery Capacity Bar Graph operates as follows LED 1 When the battery capacity is 20 the L...

Page 6: ...ction Labeled Load 1 Load 2 The locking and Always On receptacles Labeled Load 3 do not support the Load Shed ding Function NOTE The locking recptacle is not on all models 7 The input circuit breaker...

Page 7: ...tteries is complete See Connecting your Equipment NOTE If you are using an External Battery Pack with this UPS series the UPS must be configured so that the UPS will report the correct estimated runti...

Page 8: ...e UPS On the backside of the front panel push the LCD panel out wards the panel will pop out Position the LCD panel so that it reads in the up right position Re install the front panel on the UPS 8 Th...

Page 9: ...e T network single line phone Fax or Modem line to the RJ11 45 modular connectors on the rear panel of the UPS This connection will require another length of telephone or network cable The cable comin...

Page 10: ...ad 1 Load 2 The user can control the two segments individually or both at the same time The Load Shedding Function is controllable by the Power Monitoring Software or the SNMP card NOTE The output seg...

Page 11: ...ps after UPS restarts reduce the load on the UPS UPS operates in battery mode only even though there isAC present The AC normal icon is illumi nated but there is no output Disconnect the computer cabl...

Page 12: ...e impact on battery life NOTE If there is a power interruption while replacing the hot swappable batteries with the UPS on the load will not be backed up BATTERY REPLACEMENT PROCEDURE PLEASE READ THE...

Page 13: ...mation about your unit d The serial number of your unit e Any information on the failure including LEDs that may be illuminated or error codes displayed f A description of the protected equipment incl...

Page 14: ...arge cycles and ambient temp BM0029 BM0030 8 hours to 90 after full load discharge BM0031 Battery Type Sealed Non Spillable Maintenance Free Value Regulated LeadAcid System Voltage Runtime Full Load m...

Page 15: ...ems products that are depot repaired or replaced pursuant to this warranty shall only be warranted for the unex pired portion of the warranty applying to the original product This warranty applies onl...

Page 16: ...UPS Model No E750RTXL2U Y E1000RTXL2U Y E1500RTXL2U Y E2000RTXL2U Y E3000RTXL2U Y E1500RTXLT2U Y E3000RTXLT2U Y I hereby declare that the equipment specified above conforms to the above Directive s P...

Reviews: