COMMUNICATIONS PORTS 

(RS232 and USB)

The RS232 communication port is a standard DB9 female with both RS232
and simulated contact closure capability.  The UPS will poll the port and acti-
vate the port for RS232 or contact closure in accordance with the type of
cable it finds connected to the port.  To change the port configuration requires
the unit be turned off and restarted with the desired cable connected.  The
pinout for the port is depicted per the chart below:
Pin 1: Simulated contact closure Low Battery Warning, NO
Pin 2: /TXD
Pin 3: /RXD and receive UPS shutdown command (connect to pin 9 for 4-
seconds.  The shutdown command is only active in the battery mode)
Pin 4: Not Used
Pin 5: Ground
Pin 6: Not Used
Pin 7: Not Used
Pin 8: Simulated contact closure AC fail, NO
Pin 9: Atx Signal (high level: +12V +/-2V, low level: -15V +/- -2V)

DIPSWITCH SETTINGS

The dipswitch setting may be changed by the user to set the desired Inverter
(On-Battery) output voltage.  The dipswitch must be set to the desired Inverter
(On-Battery) output voltage and then the UPS must be turned off and restarted
to reconfigure the microprocessor and save the changes.  The Inverter (On-
Battery) output voltage setting can be either 120VAC (208VAC) default or
125VAC (240VAC).  Changing the Inverter (On-Battery) output voltage to
125VAC, will also change the Buck setpoint.  Changing the Inverter (On-
Battery) output voltage to 240VAC, will also change the Brownout, Boost, Buck
and Overvoltage setpoints.

SELF TEST

The self test feature is useful to verify the correct operation of the UPS and the
condition of the batteries.  With the UPS in the AC normal mode, press and
hold the On/Off/Test Button for four beeps, then release the button.  The UPS
will perform a ten-second self test.  During the self test, the UPS will switch to
the battery mode and the On-Battery icon will illuminate and the audible alarm
will sound.  The length of the test that is automatically performed every two
weeks is longer than the start-up or user invoked test.  This test will run for
approximately fifteen-seconds to measure the battery’s capability to provide
an acceptable amount of runtime.  If the UPS fails a self test, one of the icons
will remain illuminated indicating the type of problem.  

NOTE: 

 The UPS will

automatically perform a self test on start-up and every two weeks.

LOAD SHEDDING FUNCTION

The output receptacles are electrically wired into two segments to support the
"Load Shedding Function" (Labeled Load 1 & Load 2).  The user can control
the two segments individually or both at the same time.  The Load Shedding
Function is controllable by the Power Monitoring Software or the SNMP card.

NOTE:

  The output segment labeled Load 3 does not support the "Load Shed-

ding Function".

TURNING THE UNIT ON/OFF

On / Off / Test Button

Press and release the On/Off/Test Button after one beep to turn the UPS on
and supply power to the load.  

NOTE:

  The input circuit breaker (on the rear

panel) MUST be on for the 208V models.  The load is immediately powered
while the UPS runs a five-second self test.  Press and release the On/Off/Test
Button after one beep to turn the UPS off.  

NOTE:

  Turn the input circuit

breaker (on the rear panel) off for the 208V models.  The UPS will continue to
charge the batteries whenever it is plugged into a wall outlet and there is
acceptable AC voltage present.  

NOTE:

  The input circuit breaker (on the rear

panel) MUST be on for the 208V models.

The UPS will charge the batteries with the UPS in the on or off position as long
as the UPS is plugged into the wall outlet and there is an acceptable AC voltage
present (80 - 164VAC/150 - 271VAC).  

NOTE:

  The input circuit breaker

MUST be in the on position for the 208V models.  When a blackout, brownout,
or an overvoltage condition occurs; the UPS will transfer to the battery mode,
the On-Battery icon will illuminate and the audible alarm will sound once every
ten-seconds indicating that the commercial power is lost or unacceptable.
When the commercial power returns or is at an acceptable level, the UPS will
automatically transfer back to the AC normal mode and start recharging the
batteries.  During an extended outage when there is approximately two-min-
utes of backup time remaining the audible alarm will sound twice every five-
seconds.  This Low Battery Warning is letting the user know that they should
save all open files and turn off their computer.  When the batteries reach the
predetermined level the UPS will automatically shutdown protecting the batter-
ies from over discharging.  Once the commercial power returns the UPS will
automatically restart, providing safe usable power to the connected equipment
and start recharging the batteries.

POWER MONITORING SOFTWARE

The UPS comes with a Power Monitoring Software CD.  See the software CD
for the installation of the Power Monitoring Software.

USB PORT

The USB protocol is HID.  The HID USB driver is standard in the Windows OS.
Simply plug the USB cable into the UPS and the computer then follow the
prompts on the screen.  

NOTE:

   

When using the UPS's USB port with

Windows XP, 7 or 8 the Power Options in the Control Panel may need to
be configured.

Summary of Contents for Enterprise Plus LCD RTXL UPS Series

Page 1: ...r s Manual Enterprise Plus LCD RTXL UPS Series Para Systems Inc 1455 Lemay Dr Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com PN 34000431...

Page 2: ...s and Indicators 6 3 Installation 9 4 Operation 15 5 Troubleshooting 19 6 Replacing the Battery 20 7 Obtaining Service 23 8 Specifications 24 9 Configurable Parameters Settings 26 10 Limited Product W...

Page 3: ...ouble free service Please read this manual before installing your Enterprise Plus Series UPS models E750RTXL2U E1000RTXL2U E1500RTXL2U E1500RTXLT2U E2000RTXL2U E3000RTXL2U E3000RTXLT2U as it provides...

Page 4: ...ce in a residential installation This equip ment generates and uses radio frequency and if not installed and used properly that is in strict accordance with the manufacturer s instructions this equip...

Page 5: ...l be illuminated and the UPS will sound a constant alarm to indicate that there is an Overload condi tion The Battery Capacity Bar Graph operates as follows LED 1 When the battery capacity is 20 the L...

Page 6: ...ction Labeled Load 1 Load 2 The locking and Always On receptacles Labeled Load 3 do not support the Load Shed ding Function NOTE The locking recptacle is not on all models 7 The input circuit breaker...

Page 7: ...tteries is complete See Connecting your Equipment NOTE If you are using an External Battery Pack with this UPS series the UPS must be configured so that the UPS will report the correct estimated runti...

Page 8: ...e UPS On the backside of the front panel push the LCD panel out wards the panel will pop out Position the LCD panel so that it reads in the up right position Re install the front panel on the UPS 8 Th...

Page 9: ...e T network single line phone Fax or Modem line to the RJ11 45 modular connectors on the rear panel of the UPS This connection will require another length of telephone or network cable The cable comin...

Page 10: ...ad 1 Load 2 The user can control the two segments individually or both at the same time The Load Shedding Function is controllable by the Power Monitoring Software or the SNMP card NOTE The output seg...

Page 11: ...ps after UPS restarts reduce the load on the UPS UPS operates in battery mode only even though there isAC present The AC normal icon is illumi nated but there is no output Disconnect the computer cabl...

Page 12: ...e impact on battery life NOTE If there is a power interruption while replacing the hot swappable batteries with the UPS on the load will not be backed up BATTERY REPLACEMENT PROCEDURE PLEASE READ THE...

Page 13: ...mation about your unit d The serial number of your unit e Any information on the failure including LEDs that may be illuminated or error codes displayed f A description of the protected equipment incl...

Page 14: ...arge cycles and ambient temp BM0029 BM0030 8 hours to 90 after full load discharge BM0031 Battery Type Sealed Non Spillable Maintenance Free Value Regulated LeadAcid System Voltage Runtime Full Load m...

Page 15: ...ems products that are depot repaired or replaced pursuant to this warranty shall only be warranted for the unex pired portion of the warranty applying to the original product This warranty applies onl...

Page 16: ...UPS Model No E750RTXL2U Y E1000RTXL2U Y E1500RTXL2U Y E2000RTXL2U Y E3000RTXL2U Y E1500RTXLT2U Y E3000RTXLT2U Y I hereby declare that the equipment specified above conforms to the above Directive s P...