Short instruction
Configuration options, Table A:
The following criteria can be set for each smoke sensor / sampling pipe. Also, the criteria for day/night control can be separately set.
Configuration changes are saved on one of the freely programmable switch settings
X01
to
X03
.
Sector
• Parameter
Default
Setting
Range
Resolution /
Levels
Saving after
change
Alarm
• Alarm threshold (dependent on smoke sensor
type and response class according to EN 54-5 or
NFPA 72)
C11 / C12
0.02 – 10%/m (0.006 –3 .15%/ft)
0.1 – 10%/m (0.03 – 3.15%/ft)
0.5 – 10%/m (0.15 – 3.15%/ft)
0.001%/m
(0.0003%/ft)
X01 – X03
• Smoke level average value formation
4 s
1 – 10 s
1 s
X01 – X03
• Alarm delay
2 s
0 s – 60 s
1 s
X01 – X03
• Alarm self-hold
On
On/Off
X01 – X03
Pre-signal
• Pre-signal 1 On/Off
On
On/Off
X01 – X03
• Pre-signal 2 On/Off
On
On/Off
X01 – X03
• Pre-signal 3 On/Off
On
On/Off
X01 – X03
• Pre-signal 1 (100% = alarm threshold)
30%
10 – 90%
10%
X01 – X03
• Pre-signal 2 (100% = alarm threshold)
50%
VS 1 + 10 – 90%
10%
X01 – X03
• Pre-signal 3 (100% = alarm threshold)
70%
VS 2 + 10 – 90%
10%
X01 – X03
• Pre-signal delay (VS 1 – VS 3)
2 s
0 s – 60 s
1 s
X01 – X03
• Pre-signal self-hold
Off
Off/On
X01 – X03
Smoke sensor dust/dirt
• Smoke sensor dust On/Off
On
On/Off
X01 – X03
• Smoke sensor dirt On/Off
On
On/Off
X01 – X03
• Dust threshold (% of Al)
50%
5 – 60%
5%
X01 – X03
• Dirt threshold (% of Al)
75%
65 – 90%
5%
X01 – X03
• Dust self-hold
On
On/Off
X01 – X03
• Dirt self-hold
On
On/Off
X01 – X03
• Fault delay of smoke sensor
30 s
0 s – 60 s
1 s
X01 – X03
Airflow monitoring
• LS-Ü blockage On/Off
On
On/Off
X01 – X03
• LS-Ü pipe breakage On/Off
On
On/Off
X01 – X03
• LS-Ü sensitivity
±20%
±10 – ±70%
± 10%
X01 – X03
• LS-Ü average value formation
20 s
1 – 30 s
1 s
X01 – X03
• LS-Ü delay time
300 s
2 min – 60 min
10 s / 1 min
X01 – X03
The default settings of the LS-Ü sensitivity and LS-Ü delay time correspond to the above specifications for switch
settings
A01
to
C32
. Increased values are configured for switch settings
W01
to
W48
; these are
not
tested for EN or
NFPA 72 compliance (see Technical Description FHB 34 (908142), section 4.4.4.4).
Configuration options, Table B:
The following criteria apply to the entire AMX5000. Saving a configuration after changes is performed in the context of the
adaptations in Table A on one of the freely programmable switch settings
X01
to
X03
.
Sector
• Parameter
Default
Setting
Range
Resolution /
Levels
Saving after
change
Autolearning
• Autolearning On/Off
Off
On
X01 – X03
• Autolearning duration
3 days
1 min to 14 days
min, h, days
X01 – X03
• Autolearning factor (of measured Al threshold)
1.5
1.1 – 10 x
X01 – X03
Day/night control
• Day/night control On/Off
Off
On/Off
X01 – X03
• Day start time
06:00
00:00 – 24:00
15 min
X01 – X03
• Night start time
20:00
00:00 – 24:00
15 min
X01 – X03
General faults
• Lithium battery / clock fault
On
On/Off
X01 – X03
Ventilator
• Fan speed
Level III
Level I to V
1
X01 – X03