Configuration options, Table A:

 

The following criteria can be set for each smoke sensor / sampling pipe. Also, the criteria for day/night control can be separately set.

Configuration changes are saved on one of the freely programmable switch settings 

X01

 to 

X03

.

Sector

•   Parameter

Default
Setting

Range

Resolution /

Levels

Saving after 

change

Alarm

•   Alarm threshold (dependent on smoke sensor

       type and response class according to EN 54-5 or 
     NFPA 72)

C11 / C12

0.02 – 10%/m (0.006 –3 .15%/ft)

0.1 – 10%/m (0.03 – 3.15%/ft)
0.5 – 10%/m (0.15 – 3.15%/ft)

0.001%/m 

(0.0003%/ft)

X01 – X03

•   Smoke level average value formation

4 s

1 – 10 s

1 s

X01 – X03

•   Alarm delay

2 s

0 s – 60 s

1 s

X01 – X03

•   Alarm self-hold

On

On/Off

X01 – X03

Pre-signal

•  Pre-signal 1 On/Off

On

On/Off

X01 – X03

•  Pre-signal 2 On/Off

On

On/Off

X01 – X03

•  Pre-signal 3 On/Off

On

On/Off

X01 – X03

•  Pre-signal 1 (100% = alarm threshold)

30%

10 – 90%

10%

X01 – X03

•  Pre-signal 2 (100% = alarm threshold)

50%

VS 1 + 10 – 90%

10%

X01 – X03

•  Pre-signal 3 (100% = alarm threshold)

70%

VS 2 + 10 – 90%

10%

X01 – X03

•  Pre-signal delay (VS 1 – VS 3)

2 s

0 s – 60 s

1 s

X01 – X03

•  Pre-signal self-hold

Off

Off/On

X01 – X03

Smoke sensor dust/dirt

•  Smoke sensor dust On/Off 

On

On/Off

X01 – X03

•  Smoke sensor dirt On/Off 

On

On/Off

X01 – X03

•  Dust threshold (% of Al)

50%

5 – 60%

5%

X01 – X03

•  Dirt threshold (% of Al) 

75%

65 – 90%

5%

X01 – X03

•  Dust self-hold

On

On/Off

X01 – X03

•  Dirt self-hold

On

On/Off

X01 – X03

•  Fault delay of smoke sensor

30 s

0 s – 60 s

1 s 

X01 – X03

Airflow monitoring

•  LS-Ü blockage On/Off

On

On/Off

X01 – X03

•  LS-Ü pipe breakage On/Off

On

On/Off

X01 – X03

•  LS-Ü sensitivity

±20% 

±10 – ±70%

± 10%

X01 – X03

•  LS-Ü average value formation

20 s

1 – 30 s

1 s

X01 – X03

•  LS-Ü delay time 

300 s 

2 min – 60 min

10 s / 1 min

X01 – X03



The default settings of the LS-Ü sensitivity and LS-Ü delay time correspond to the above specifications for switch 

settings 

A01

 to 

C32

. Increased values are configured for switch settings 

W01

 to 

W48

; these are 

not

 tested for EN or 

NFPA 72 compliance (see Technical Description FHB 34 (908142), section 4.4.4.4).

Configuration options, Table B:

The following criteria apply to the entire AMX5000. Saving a configuration after changes is performed in the context of the 
adaptations in Table A on one of the freely programmable switch settings 

X01 

to 

X03

.

Sector

•   Parameter

Default 
Setting

Range

Resolution /

Levels

Saving after 

change

Autolearning

•  Autolearning On/Off

Off

On

X01 – X03

•  Autolearning duration

3 days

1 min to 14 days

min, h, days

X01 – X03

•  Autolearning factor (of measured Al threshold)

1.5

1.1 – 10 x

X01 – X03

Day/night control

•  Day/night control On/Off 

Off

On/Off

X01 – X03

•  Day start time

06:00 

00:00 – 24:00

15 min

X01 – X03

•  Night start time

20:00

00:00 – 24:00

15 min

X01 – X03

General faults

•  Lithium battery / clock fault 

On

On/Off

X01 – X03

Ventilator

•  Fan speed 

Level III

Level I to V

1

X01 – X03

 

Summary of Contents for AMX5000 Series

Page 1: ... modules can be added KMX5005 RK Relay Interface Module with 5 relays max 2 units MMX5005 Memory module Other In preparation interface module The AMX5000 can be linked to a higher level FACP by means of relays The AMX5000 can be connected to a fire alarm system by using potential free contacts Integration in the System FMZ5000 Loop Ap is possible by mo dules Displaying status and control of the AM...

Page 2: ...ning is prevented by the anti twist rib on the smoke sensor housing The smoke sensors are fastened with the two lock clamps in the AMX housing The electrical connection to the Main Board is accomplished with the supplied ribbon cable The smoke sensor chamber II on the AMX5001 and AMX5101 only one smoke sensor remains open insect protection screens and lock clamps are not fitted air channels are cl...

Page 3: ...n Alarm Fault Det dusty dirty Smoke level green red yell yell yell System off no voltage System inactive external reset On 1 2 T Smoke sensor off from FACP On 1 2 T Idle state On Blockage pipe breakage delay time running On 1 T Blockage pipe breakage fault triggered On On Fan tacho signal lacking On On Fault triggered On On Pre signal 1 AMX5001 5002 On 2 T Pre signal 2 AMX5001 5002 On 1 T Pre sign...

Page 4: ... AMX to the last T piece cross Max length from AMX to the farthes sampling hole Number of sampling holes per sampling branch Max total length of the sampling pipe per pipe network smoke sensor 1 tube 2 tube 1 tube 2 tube I 1 A11 A12 W01 W04 W05 W08 20 0 03 0 01 50 m 164 ft 1 7 50 m 164 ft U T 1 A11 A12 W01 W04 W05 W08 20 0 03 0 01 3 3 65 6 1 20 m 40 m 131 ft 1 4 80 m 262 ft H 1 A11 A12 W01 W04 W05...

Page 5: ...4 0 7 0 12 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 2 5 2 5 4 0 7 0 13 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 2 5 2 5 4 0 7 0 14 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 2 5 4 0 7 0 15 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 4 0 7 0 16 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 5 4 0 7 0 U T shaped sampling pipes Number of sampling holes per sampling branch Hole diameter in mm for th...

Page 6: ...of Al 75 65 90 5 X01 X03 Dust self hold On On Off X01 X03 Dirt self hold On On Off X01 X03 Fault delay of smoke sensor 30 s 0 s 60 s 1 s X01 X03 Airflow monitoring LS Ü blockage On Off On On Off X01 X03 LS Ü pipe breakage On Off On On Off X01 X03 LS Ü sensitivity 20 10 70 10 X01 X03 LS Ü average value formation 20 s 1 30 s 1 s X01 X03 LS Ü delay time 300 s 2 min 60 min 10 s 1 min X01 X03 The defau...

Page 7: ... dirty Relay 5 2nd KMX5005 RK Sampling tube II pipe blockage Reset button On Off On On Off Start initial reset On Off Relay allocation configuration options The following criteria can be programmed on a max of 11 relays 1 Main Board unit on AMX5001and AMX5101 6 units on 1st KMX5005 RK 5 units on 2nd KMX5005 RK Smoke sensor I LS Ü I Smoke sensor II LS Ü II General Smoke sensor I alarm Smoke sensor ...

Page 8: ... is now ready for operation Re programming Example Response class B system limit 2 AMX5102 2 sam pling tubes required switch setting b22 Initial reset Measurements commissioning protocol Carry out the following measurements Measure operating voltage on terminals 1 2 if redun dant supply then also terminals 3 4 target value 12 3 to 13 8 VDC in 12 VDC operation or 21 6 to 27 6 VDC in 24 VDC operatio...

Page 9: ...be car ried out for both sampling pipes Brief description Article number Aspirating smoke detector AMX5001 908095 Aspirating smoke detector AMX5002 908096 Aspirating smoke detector AMX5101 908097 Aspirating smoke detector AMX5102 908098 Smoke sensor OMX5005 0 5 m 10 m 0 15 ft 3 15 ft 908099 Smoke sensor OMX5010 0 1 m 10 m 0 03 ft 3 15 ft 908100 Smoke sensor OMX5020 0 02 m 10 m 0 006 ft 3 15 ft 908...

Page 10: ... IEC 529 EN 60529 1991 54 IP Ambient conditions acc to IEC 721 3 3 EN 60721 3 3 1995 3K5 3Z1 Class Extended ambient conditions Detector housing temperature range 30 60 4 140 C F Sampling pipe temperature range 30 60 4 140 C F Max approved temperature fluctuation in detector housing and sampling pipe operation 20 68 C F Max storage temperature deflector housing no condensation 30 70 4 158 C F Ambie...

Reviews: