FHK34, 908143

AMX5000

Short instruction

Commissioning

 

When commissioning the AMX5000, it is necessary to perform
an initial reset in order to collect basic data (e.g. connected
sampling pipe, motor data). An initial reset also performs an au-
tomatic adjustment of the airflow monitoring on the connected
sampling pipe(s).
If the AMX5000 is operated within the system limits without
“HELIOS PipeCalc” calculation, commissioning with the 

“Ea-

syConfig” method

 can be carried out directly on the

AMX5000. 
For projects in which the “HELIOS PipeCalc” calculation soft-
ware was used or in which customer-specific adaptations have
to be made in the device configuration, the 

“HELIOS Config”

configuration software has to be used. 

Starting up

 

Before the AMX5000 is switched on, it is absolutely
necessary that all of the required measures have
been performed (see FHB 34 (908142), section 7.1). 

• sampling pipe correctly mounted and connected

to the AMX; 

• smoke sensors and expansion modules installed in
   the AMX and connected;

• isolation strip on the Lithium battery (MAIN
   BOARD) removed.

Sequence and procedure for starting up:

 

1.

Switch on supply voltage (FACP); while the fan accelerates
incrementally to its final speed (takes about 100 s), the next
procedure can be carried out. 

The system is immediately

armed for alarm.

2.

“EasyConfig”: 

select necessary switch setting for operati-

on according to 

“System limit table”

 (e.g. 

“b2”

 see

“Re-programming”

.

- or:

“HELIOS Config”:

 after adapting the configuration (alarm

threshold according to “HELIOS PipeCalc” and other crite-
ria in Tables A and B), select switch setting 

“X01”

, “X02"

or 

“X03”

.

3.

Set date and time via MAIN BOARD with “EasyConfig” or
from “HELIOS Config” (adoption by PC).

4.

Following a 

minimum waiting time of 5 min

 after swit-

ching on, an initial reset must be performed (possible only
via MAIN BOARD) 



see 

“Initial reset”

.

5.

The AMX5000 is now ready for operation. 

Re-programming

Example: Response class B, system limit 2, AMX5102 (2 sam-
pling tubes), required switch setting

 b22

.

Initial reset

Measurements / commissioning protocol

Carry out the following measurements: 
• Measure operating voltage on terminals 1 (+), 2 (-) (if redun-

dant supply, then also terminals 3 & 4) 



target value = 12.3

to 13.8 VDC (in 12 VDC operation) or 21.6 to 27.6 VDC (in
24 VDC operation).

• Airflow values in switch settings 

V

 (see Technical Description

FHB 34 (908142), section 7.6.1) 

• The commissioning protocol is like a personal history of the

AMX5000 and should therefore be filled out conscientiously
and completely and stored in the AMX5000. If required, a
copy can be made and stored in the installation dossier. 

Measure

Display /
indication

Procedure
Remark

Switch settings 

W01

 to 

W48

 may be used only after 

consulting with the manufacturer. The configured 
values they contain concerning airflow monitoring 
are 

not

 tested in accordance with EN (or NFPA). 

6.

Press the "UP” 
button

Flashing 

C32

•  Display of the default

    setting

7.

Press "UP” 
twice until dis-
play shows 

b

In sequence:

A / b

•  Display switch setting

    group 

b

8.

Press the "OK" 
button

b11 

•  Display of the smallest
  possible setting in group
  

b

9.

Press "UP” 
until display 
shows 

b22

In sequence:

b11 / b12 / b21 
/ b22
 

•  Display of the possible
   settings in group 

b

10.

Press the "OK" 
button

Flashing  

b - - 

(approx. 4 x)

•  New setting is pro-
   grammed 

11.

Check: Press 
the "UP” button

Flashing 

b22

•  Display of the new set-
   ting

Measure

Display /
indication

Procedure
Remark

Before performing an initial reset after switching on 
the AMX5000, a 

waiting time of at least 5 min

 

must be observed.  

1.

Press the "UP” 
button

Flashing 

C32 

or other

•  Display of the default

    setting or the installa-
    tion-specific switch set-
    ting

2.

Press "UP” 
several times 
until display 
shows 

U

In sequence:

A to U

•  Display of the switch

    setting group 

U

3.

Press the "OK" 
button

U01 

•  Display initial reset On

4.

Press the "OK" 
button again

Flashing 

U - -

 

(5 to max. 120 
s)

 

•  Initial reset runs

5.

Wait

Flashing  point

 

(watchdog indi-
cator)

•  Initial reset completed 

 

 

 

Summary of Contents for AMX5000 Series

Page 1: ... modules can be added KMX5005 RK Relay Interface Module with 5 relays max 2 units MMX5005 Memory module Other In preparation interface module The AMX5000 can be linked to a higher level FACP by means of relays The AMX5000 can be connected to a fire alarm system by using potential free contacts Integration in the System FMZ5000 Loop Ap is possible by mo dules Displaying status and control of the AM...

Page 2: ...ning is prevented by the anti twist rib on the smoke sensor housing The smoke sensors are fastened with the two lock clamps in the AMX housing The electrical connection to the Main Board is accomplished with the supplied ribbon cable The smoke sensor chamber II on the AMX5001 and AMX5101 only one smoke sensor remains open insect protection screens and lock clamps are not fitted air channels are cl...

Page 3: ...n Alarm Fault Det dusty dirty Smoke level green red yell yell yell System off no voltage System inactive external reset On 1 2 T Smoke sensor off from FACP On 1 2 T Idle state On Blockage pipe breakage delay time running On 1 T Blockage pipe breakage fault triggered On On Fan tacho signal lacking On On Fault triggered On On Pre signal 1 AMX5001 5002 On 2 T Pre signal 2 AMX5001 5002 On 1 T Pre sign...

Page 4: ... AMX to the last T piece cross Max length from AMX to the farthes sampling hole Number of sampling holes per sampling branch Max total length of the sampling pipe per pipe network smoke sensor 1 tube 2 tube 1 tube 2 tube I 1 A11 A12 W01 W04 W05 W08 20 0 03 0 01 50 m 164 ft 1 7 50 m 164 ft U T 1 A11 A12 W01 W04 W05 W08 20 0 03 0 01 3 3 65 6 1 20 m 40 m 131 ft 1 4 80 m 262 ft H 1 A11 A12 W01 W04 W05...

Page 5: ...4 0 7 0 12 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 2 5 2 5 4 0 7 0 13 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 2 5 2 5 4 0 7 0 14 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 2 5 4 0 7 0 15 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 4 0 7 0 16 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 5 4 0 7 0 U T shaped sampling pipes Number of sampling holes per sampling branch Hole diameter in mm for th...

Page 6: ...of Al 75 65 90 5 X01 X03 Dust self hold On On Off X01 X03 Dirt self hold On On Off X01 X03 Fault delay of smoke sensor 30 s 0 s 60 s 1 s X01 X03 Airflow monitoring LS Ü blockage On Off On On Off X01 X03 LS Ü pipe breakage On Off On On Off X01 X03 LS Ü sensitivity 20 10 70 10 X01 X03 LS Ü average value formation 20 s 1 30 s 1 s X01 X03 LS Ü delay time 300 s 2 min 60 min 10 s 1 min X01 X03 The defau...

Page 7: ... dirty Relay 5 2nd KMX5005 RK Sampling tube II pipe blockage Reset button On Off On On Off Start initial reset On Off Relay allocation configuration options The following criteria can be programmed on a max of 11 relays 1 Main Board unit on AMX5001and AMX5101 6 units on 1st KMX5005 RK 5 units on 2nd KMX5005 RK Smoke sensor I LS Ü I Smoke sensor II LS Ü II General Smoke sensor I alarm Smoke sensor ...

Page 8: ... is now ready for operation Re programming Example Response class B system limit 2 AMX5102 2 sam pling tubes required switch setting b22 Initial reset Measurements commissioning protocol Carry out the following measurements Measure operating voltage on terminals 1 2 if redun dant supply then also terminals 3 4 target value 12 3 to 13 8 VDC in 12 VDC operation or 21 6 to 27 6 VDC in 24 VDC operatio...

Page 9: ...be car ried out for both sampling pipes Brief description Article number Aspirating smoke detector AMX5001 908095 Aspirating smoke detector AMX5002 908096 Aspirating smoke detector AMX5101 908097 Aspirating smoke detector AMX5102 908098 Smoke sensor OMX5005 0 5 m 10 m 0 15 ft 3 15 ft 908099 Smoke sensor OMX5010 0 1 m 10 m 0 03 ft 3 15 ft 908100 Smoke sensor OMX5020 0 02 m 10 m 0 006 ft 3 15 ft 908...

Page 10: ... IEC 529 EN 60529 1991 54 IP Ambient conditions acc to IEC 721 3 3 EN 60721 3 3 1995 3K5 3Z1 Class Extended ambient conditions Detector housing temperature range 30 60 4 140 C F Sampling pipe temperature range 30 60 4 140 C F Max approved temperature fluctuation in detector housing and sampling pipe operation 20 68 C F Max storage temperature deflector housing no condensation 30 70 4 158 C F Ambie...

Reviews: