background image

AMX5000

 

FHK34, 908143

3 / 10

Short instruction

Fig. 3 Deploying the smoke sensors

Displays on the control unit

Several LEDs on the control unit indicate the current state of
the AMX5000. The table below lists only the states for the
AMX5001 and AMX5101 (one smoke sensor / one sampling
pipe). Except for the operation display, the displays are doubled
for the AMX5002 and AMX5102 (I and II). 

Displays on the Main Board

On the Main Board there is a 3-digit segment display which can 
have the following outputs and displays: 

flashing point and 

AL

 = Autolearning running;

flashing point and point continuously lit = day/night control
active;

switch setting 

E

 = event memory (99 events 

E01

 to 

E99

),

for more information see FHB 34 (908142), section 8.5.3; 

switch setting 

F

 = operating software version (firmware), for

more information see FHB 34 (908142), section 7.3.6;

pushbutton “UP” = the set configuration (

A11

 to 

C32

,

W01

to 

W48

,

 X01

 to 

X03

), see also 

“Programming”

;

switch setting 

V

 = airflow values (airflow rate), for more in-

formation see Technical Description, section 7.6.1

Programming

The AMX5000 has several switch settings which are configu-
red with permanently assigned parameters: 

normative system limits according to EN 54-20, Class A to
C (or NFPA 72), settings 

A11

 to 

C32

;

non-normative system limits, settings 

W01

 to 

W48

;

configurable settings for saving settings after using "HELI-

       OS PipeCalc" and/or changing the device configuration via
       the “HELIOS Config” configuration software, 

X01

 to 

X03

The parameters are configured post-factory with de-
faultstates and values so that the triggering proper-
ties comply with EN 54-20 (NFPA 72). Changing the
parameters may result in non-compliance with EN
54-20 (NFPA 72). Any adjustments or modifications to

                    the AMX5000 via“HELIOS Config” may be performed
                only by the manufacturer or by persons under the
                supervision of and trained by the manufacturer.

Switch settings on the Main Board

Function / state

Op

eratio

n

Alarm

Fau

lt

Det. d

u

st

y / di

rt

y

Smok

e level 

green red yell. yell. yell.

System off (no voltage)

System inactive (external reset)

On

1

/

2

 T

Smoke sensor off (from FACP)

On

1

/

2

 T

Idle state 

On

Blockage / pipe breakage, 
delay time running 

 

On

1 T

Blockage / pipe breakage, fault 
triggered

On

On

Fan tacho signal lacking

On

On

Fault triggered

On

On

Pre-signal 1 (AMX5001/ 5002) 

On

2 T

Pre-signal 2 (AMX5001/ 5002)

On

1 T

Pre-signal 3 (AMX5001/ 5002)

On

1

/

2

 T

Smoke level 1–10 (AMX5101/
5102) 

On

On

Pre-signal 1, 2, 3 (AMX5101/
5102) 

On

1 T

Alarm

On

On

Dusty smoke sensor

On

1 T

Dirty smoke sensor

On

1

/

2

 T

Smoke sensor fault 

On

On

Additional for AMX5101 and AMX5102 



No fault triggered (triggers only after the delay time 

expires 

 “Fault” LED display continuously lit). 



The LED of the respective smoke level 1–10 (cor-

responds to 10–100% of alarm threshold) is conti-
nuously lit when exceeded. If a pre-signal is
programmed on this level, the LED subsequently
begins to flash (default: VS 1 = level 3, VS 2 = level
5, VS 3 = level 7).

= Flashing indicator; ½s cycle / 1s cycle / 2s cycle 

 

Anti-twist rib

Flat cable

Smoke sensor chamber  I

Smoke sensor chamber  II

Smoke sensor I

Smoke sensor II

Connection for
smoke sensor I / II

AMB 35

Insect protection scree

Lock clamps

II

II

I

I

Pos. Range / Display

Purpose

A

A11 / A12

Normative system limits 
according to EN 54-20, 
Class A (or NFPA 72) 

b

b11 / b12 / b21 / b22

Normative system limits in 
compliance with EN 54-20, 
Class B (or NFPA 72) 

C

C11 / C12 / C21 / C22 / 
C31 / C32

Normative system limits in 
compliance with EN 54-20, 
Class C (or NFPA 72)

E

E01

 to 

E99

 

 

G00

 to 

G99

Event memory 

E01 – E99

 Event group 

G00 – G99

F

F00

 to 

F99

 (3 x)

Display of operating soft-
ware version (firmware)

o

o00

Log off expansion modules 
(optional modules)

T

Y05

 to 

Y99 / M01

 to 

M12

d01

 to 

d31 / H00

 to 

H23

M00

 to 

M59

 

Setting the date
Setting the time

U

U01

Execute initial reset 

V

V01 / V02

, each

000

 to 

255

Output airflow rate in % 
Pipe I (=

V01

), pipe II (=

V02

)

W

W11

 to 

W48

 

Non-normative system 
limits 

X

X01 

to 

X03

Configurable switch set-
tings 

The table lists only the available switch settings.
Information about entry procedure is found in Tech-
nical Description FHB 34 (908142), section 8.3. 

 

 

Summary of Contents for AMX5000 Series

Page 1: ... modules can be added KMX5005 RK Relay Interface Module with 5 relays max 2 units MMX5005 Memory module Other In preparation interface module The AMX5000 can be linked to a higher level FACP by means of relays The AMX5000 can be connected to a fire alarm system by using potential free contacts Integration in the System FMZ5000 Loop Ap is possible by mo dules Displaying status and control of the AM...

Page 2: ...ning is prevented by the anti twist rib on the smoke sensor housing The smoke sensors are fastened with the two lock clamps in the AMX housing The electrical connection to the Main Board is accomplished with the supplied ribbon cable The smoke sensor chamber II on the AMX5001 and AMX5101 only one smoke sensor remains open insect protection screens and lock clamps are not fitted air channels are cl...

Page 3: ...n Alarm Fault Det dusty dirty Smoke level green red yell yell yell System off no voltage System inactive external reset On 1 2 T Smoke sensor off from FACP On 1 2 T Idle state On Blockage pipe breakage delay time running On 1 T Blockage pipe breakage fault triggered On On Fan tacho signal lacking On On Fault triggered On On Pre signal 1 AMX5001 5002 On 2 T Pre signal 2 AMX5001 5002 On 1 T Pre sign...

Page 4: ... AMX to the last T piece cross Max length from AMX to the farthes sampling hole Number of sampling holes per sampling branch Max total length of the sampling pipe per pipe network smoke sensor 1 tube 2 tube 1 tube 2 tube I 1 A11 A12 W01 W04 W05 W08 20 0 03 0 01 50 m 164 ft 1 7 50 m 164 ft U T 1 A11 A12 W01 W04 W05 W08 20 0 03 0 01 3 3 65 6 1 20 m 40 m 131 ft 1 4 80 m 262 ft H 1 A11 A12 W01 W04 W05...

Page 5: ...4 0 7 0 12 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 2 5 2 5 4 0 7 0 13 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 2 5 2 5 4 0 7 0 14 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 2 5 4 0 7 0 15 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 4 0 7 0 16 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 5 4 0 7 0 U T shaped sampling pipes Number of sampling holes per sampling branch Hole diameter in mm for th...

Page 6: ...of Al 75 65 90 5 X01 X03 Dust self hold On On Off X01 X03 Dirt self hold On On Off X01 X03 Fault delay of smoke sensor 30 s 0 s 60 s 1 s X01 X03 Airflow monitoring LS Ü blockage On Off On On Off X01 X03 LS Ü pipe breakage On Off On On Off X01 X03 LS Ü sensitivity 20 10 70 10 X01 X03 LS Ü average value formation 20 s 1 30 s 1 s X01 X03 LS Ü delay time 300 s 2 min 60 min 10 s 1 min X01 X03 The defau...

Page 7: ... dirty Relay 5 2nd KMX5005 RK Sampling tube II pipe blockage Reset button On Off On On Off Start initial reset On Off Relay allocation configuration options The following criteria can be programmed on a max of 11 relays 1 Main Board unit on AMX5001and AMX5101 6 units on 1st KMX5005 RK 5 units on 2nd KMX5005 RK Smoke sensor I LS Ü I Smoke sensor II LS Ü II General Smoke sensor I alarm Smoke sensor ...

Page 8: ... is now ready for operation Re programming Example Response class B system limit 2 AMX5102 2 sam pling tubes required switch setting b22 Initial reset Measurements commissioning protocol Carry out the following measurements Measure operating voltage on terminals 1 2 if redun dant supply then also terminals 3 4 target value 12 3 to 13 8 VDC in 12 VDC operation or 21 6 to 27 6 VDC in 24 VDC operatio...

Page 9: ...be car ried out for both sampling pipes Brief description Article number Aspirating smoke detector AMX5001 908095 Aspirating smoke detector AMX5002 908096 Aspirating smoke detector AMX5101 908097 Aspirating smoke detector AMX5102 908098 Smoke sensor OMX5005 0 5 m 10 m 0 15 ft 3 15 ft 908099 Smoke sensor OMX5010 0 1 m 10 m 0 03 ft 3 15 ft 908100 Smoke sensor OMX5020 0 02 m 10 m 0 006 ft 3 15 ft 908...

Page 10: ... IEC 529 EN 60529 1991 54 IP Ambient conditions acc to IEC 721 3 3 EN 60721 3 3 1995 3K5 3Z1 Class Extended ambient conditions Detector housing temperature range 30 60 4 140 C F Sampling pipe temperature range 30 60 4 140 C F Max approved temperature fluctuation in detector housing and sampling pipe operation 20 68 C F Max storage temperature deflector housing no condensation 30 70 4 158 C F Ambie...

Reviews: