Astra-Z-4545

 

 

Wireless Manual Fire Alarm Call Point

 

 

Operation Manual 

 

 

 

 

 

 

 

 
This  operation  manual  is  intended  for  studying  the  operating 
principles,  proper  use,  storage,  and  maintenance  of  the 
Wireless  Manual  Fire  Alarm  Call  Point  Astra-Z-4545 
(hereinafter referred to as a detector) (Figure 1). 

 

List of Abbreviations

Astra-Zitadel System

: Astra-Zitadel on-site Wireless Intrusion 

/ Fire Detection and Alarming System; 

Astra-Zitadel  System  Control  Panel

:  Astra-Z-812M,  Astra-Z-

8945  ver.A,  Astra-8945  Pro  or  Astra-812  Pro  Control  Panel 
(with connected Astra-Z Wireless Extender); 

LT

: Astra-942 Laser Tester; 

MSS Astra-Z

: Astra-Z Monitoring Software Suite; 

MSS Astra Pro

: Astra Pro Monitoring Software Suite. 

 

1  Function 

 

1.1 

 The detector is designed for manual 

activation  of  a  fire  alarm by  pressing  the 
driving 

element, 

forming 

«Fire» 

notifications, and transmitting them to the 
Astra-Zitadel  System  Control  Panel  via 
radio. 

1.2 

Power  is  supplied  to  the  detector 

from  one  or  two  lithium-thionyl-chloride 
batteries  (primary  and  secondary),  size 
AA, voltage 3.6 V. 

 

2  Operating Principle  

  

The detector is activated by pressing the actuator 

– indestruct-

ible  plate.  After  being  pressed  the  plate  locks  in  the  pushed 
position. 

Microprocessor  forms  «Fire»  notification  in  accor-

dance with pre-set algorithm. 
The  detector  is  returned  to  standby  mode  by  returning  the 
actuator to an initial state with a key-pusher. 

 

Specification

 

 

Technical Parameters of Radio Channel

 

Operating frequency range, MHz .................. 2 400 to 2 483. 5 
Number of operating channels at 5 MHz intervals ................ 16 
Channel width, MHz ............................................................... 2 
Wireless coverage range, line-of-sight, m, min ................... 300 

 

General Technical Parameters 

 

Current consumption, mA, max: 
- with radio module OFF .................................................... 0.04 
- with radio module ON ....................................................... 105 
Battery replacement  
indication threshold, V ......................................................... 2.6 
Power supply voltage lower threshold (programmed 
deactivation threshold retaining  
battery discharge indication), V ........................................... 2.1 
Overall dimensions, mm, max ................................. 110x94x47 
Weight (without battery), kg, max ...................................... 0.17 
Primary battery average lifetime, years, min .......................... 3 
Secondary batteries set  
average lifetime, years, min .................................................... 5 

 

Operating Conditions 

 

Temperature range, 

°

C ................................ from -30 up to +55 

Relative air humidity, % ............................... up to 93 at +40 

°

without moisture condensation  

 

Delivery Set 

 

Astra-Z-4545 ................................................................... 1 pcs. 
Mortise key (large) ........................................................... 1 pcs. 
Key-pusher (small) .......................................................... 1 pcs. 
Battery ............................................................................. 2 pcs. 
Screw 

3.9×32 .................................................................. 2 pcs. 

Dowel 6×30 ..................................................................... 2 pcs. 
Operation Manual ........................................................... 1 copy 

Structure 

 

5.1 

The  detector  is  designed  as  a  block  consisting  of  a 

removable  cover  and  a  base,  made  of  high-impact  plastic 
(Figure 2). 

 

                                          Figure 2 

 

5.2 

Mounted inside the cover is a printed circuit board (PCB) 

with  radio  elements  and  slots  for  the  primary  and  secondary 
batteries.  The  recessed  part  of  the  cover  also  contains  an 
actuator  with  an  inscription  that  clearly  marks  the  place  and 
direction to be pressed 

5.3 

The upper section of the recessed part contains white or 

yellow shutter, which emerges when the actuator is pressed. 

5.4 

Mounted  on  PCB  is  a  tamper  switch  (S1button),  which 

results  in  the 

«Tampering»  notification  when  the  cover  is 

removed. 

5.5 

Mounted  on  PCB  are  LEDs  for  the  detector

’s  operability 

supervision. 

 

Notifications 

 

Table 1: Notifications processed by LEDs and Control Panel (or 
MSS interface) 
 

Notification

 

Type

 

Red

 

LED

 

White

 

LED

 

Control 

Panel

 

 
Standby 
mode start 

Lights  up 

one 

time

  for 

1  to 

40 

seconds

 

after  detector 
powering up 

Not lit 

− 

Normal 

Blinks 

one 

time

 

per 

(60±5) 
seconds

 

for  

0,2 seconds

 

Not lit 

Fire 

Lights up  

one  time

  for 

10 seconds 

Not lit 

Tampering 

Lights  up 

one 

time

  for 

0.2 

seconds

 

Not lit 

Powering up 

Not lit 

Any 

Primary battery 
failure 

Not lit 

Any  

 

Secondary 
battery failure* 

Not lit

 

Any  

 

Power failure 

Triple

 

blink 

every 

25 

seconds 

Not lit 

Base removed 

Figure 1 

Summary of Contents for Astra-Z-4545

Page 1: ...eplacement indication threshold V 2 6 Power supply voltage lower threshold programmed deactivation threshold retaining battery discharge indication V 2 1 Overall dimensions mm max 110x94x47 Weight without battery kg max 0 17 Primary battery average lifetime years min 3 Primary Secondary batteries set average lifetime years min 5 Operating Conditions Temperature range C from 30 up to 55 Relative ai...

Page 2: ...ry activation and checking period If after 40 seconds the red LED flashes with a triple blink every 25 seconds activate the battery by removing it waiting at least 30 seconds and reinserting it Warning If two batteries have been inserted replace both batteries 7 3 Registering the Detector in the Wireless Network Detector registration is required for detector identification within the wireless netw...

Page 3: ...or to the standby position Insert the key pusher firmly into the opening on the bottom edge of the detector until the actuator is released Remove the key 3 Activate test mode for communication channel supervision Press the upper button on the LT Direct the laser beam at the detector LED Irradiate the LED for 1 second After 5 seconds make sure Fire notification appears on the LED the red LED lights...

Page 4: ...he detector by any third party service except for the manufacturer 12 7 The warranty applies to the detector only All equipment from other manufacturers used with the detector including batteries is subject to its own warranty terms The manufacturer bears no responsibility for death injury property damage or other incidental or premeditated loss based on user s statement that the device failed to ...