Default is 5 sec.
UPS_HARDOFF_TOUT[s]
After UPS_VBAT_UVP_OFF_TOUT
passed motherboard is signaled to shut
down. The UPS will wait this period so
that the Motherboard can shut down
gracefully, than cut power and enter deep
sleep. This period should not be too long
to prevent battery drain.
Default is 60 sec.
UPS_SWITCHOVER_VBAT_TOUT[ms] After UPS switches to battery, can switch
back to Vin only after this time elapses.
Default is 1000ms.
UPS_SWITCHOVER_VIN_TOUT[ms]
After UPS switches to input, can switch
back to battery only after this time
elapses.
Default is 1ms.
DCHG_IMAX[mA]
Max allowed discharge current. In case
discharge current exceeds this threshold
shutdown will be initiated.
Default is 10000 mA.
CAPACITY[mAh]
Battery Capacity.
Default 7000mAh.
CHG_BAT_TYPE
The battery chemistry to be charged.
0- PbSO4 (float charge is applied)
1- LiFePO4 (float charge is not applied)
2-LiPO(float charge is not applied)
Other (float charge is not applied)
Default is 0.
CHG_VCOND[V]
Conditioning/Pre-charge voltage. Charge
current is limited to CHG_ICOND until cell
voltage exceeds this value and for at least
CHG_TCOND time .
Default is 11.2V.
CHG_ICOND[mA]
Conditioning/Precharge current. Charge
current is limited to this value until cell
voltage exceeds CHG_VCOND value and
for at least CHG_TCOND time .
Default is 100mA.
CHG_TCOND [s]
Conditioning/Precharge time. Charge
current is limited to CHG_ICOND value
until cell voltage exceeds CHG_VCOND
value and it is applied during this time.
Default is 30 sec.
CHG_IBULK[mA]
Fast charge current limit (constant current
mode)
Default is 1750mA.
CHG_BULK_STOP_VOLTAGE[V/cell]
Maximum allowed bulk charge