The message format is as follows:
Data Length:
$04
Message Type:
$85
Additional Data:
$02 = Parameter Number
$03 = MSB of the Parameter Value
$04 = LSB of the parameter value
The following examples would be from a Monitor responding to address 1:
Reporting GAIN CONTROL (parameter number $0B) = 33% or $0021:
R0104850B002100B6
Reporting relay 1 “on” Setpoint (par num $14) = 5.6 ft or $0038:
R01048514003800D6
Acknowledge (optional enhanced serial port only)
This message is a response to a host originated message to indicate that the requested change in mode or
program parameter has been successfully implemented. The message format is as follows:
Data Length:
$01
Message Type:
$F0
Additional Data:
none
Example: Monitor number 1 would respond R0101F000F2
NEGATIVE ACKNOWLEDGE
This message is a response to a host originated message to indicate that the requested operation was not
possible. The message format is as follows:
Data Length:
$01
Message Type:
$FF
Additional Data:
none
Example: Monitor number 2 would respond R0201FF0102.
Summary of Contents for InterRanger IR-200
Page 12: ...InterRanger IR 200 12 PL 545 ...
Page 18: ...InterRanger IR 200 18 PL 545 ...
Page 22: ...InterRanger IR 200 22 PL 545 ...
Page 32: ...InterRanger IR 200 32 PL 545 ...
Page 34: ...InterRanger IR 200 34 PL 545 ...
Page 38: ...InterRanger IR 200 38 PL 545 ...
Page 48: ...InterRanger IR 200 48 PL 545 ...
Page 50: ...InterRanger IR 200 50 PL 545 ...
Page 56: ...InterRanger IR 200 56 PL 545 ...