The message is formatted as follows:
Data Length:
$02
Message Type:
$07
Additional Data:
(one of the following:)
$00 - Changes the unit to the RUN
mode
$01 - Changes the unit to the PGM
mode
Expected Reply:
Acknowledge Message or Negative
Acknowledge Message
Example:
To change Monitor number 3 to the PGM mode, the following message would be transmitted
by the host: “M03020701000D”.
PROGRAM PARAMETER NUMBERS
Parameter Name
Parameter
Number
Change only in
PGM mode
Tank Depth
$01
No
Display Format
$02
Yes
Trend Graph Time Scale
$03
Yes
Echo Profile Update Rate
$04
Yes
Interface Level Averaging Cycles
$05
Yes
Trigger Point
$06
No
Median or Average
$07
Yes
Sensitivity
$08
No
Bottom Dead Zone
$09
No
Top Dead Zone
$0A
No
Gain Control
$0B
No
Maximum Transmit Gain
$0C
No
Bottom Echo in Gain Control?
$0D
No
AGC Exclusion
$0E
No
Speed of Sound Correction
$0F
No
Lost Interface Control
$10
No
Serial Address
$11
No
Baud Rate
$12
No
4 mA Level
$13
No
20 mA Level
$14
No
Relay Number 1 Function
$15
No
Relay Number 1 “on” Setpoint
$16
No
Relay Number 1 “off” Setpoint
$17
No
Relay Number 2 Function
$18
No
Relay Number 2 “on” Setpoint
$19
No
Relay Number 2 “off” Setpoint
$1A
No
Relay Number 3 Function
$1B
No
Relay Number 3 “on” Setpoint
$1C
No
Relay Number 3 “off” Setpoint
$1D
No
Relay Number 4 Function
$1E
No
Relay Number 4 “on” Setpoint
$1F
No
Relay Number 4 “off” Setpoint
$20
No
Summary of Contents for InterRanger IR-200
Page 12: ...InterRanger IR 200 12 PL 545 ...
Page 18: ...InterRanger IR 200 18 PL 545 ...
Page 22: ...InterRanger IR 200 22 PL 545 ...
Page 32: ...InterRanger IR 200 32 PL 545 ...
Page 34: ...InterRanger IR 200 34 PL 545 ...
Page 38: ...InterRanger IR 200 38 PL 545 ...
Page 48: ...InterRanger IR 200 48 PL 545 ...
Page 50: ...InterRanger IR 200 50 PL 545 ...
Page 56: ...InterRanger IR 200 56 PL 545 ...