OPERATION
INITIAL OPERATION
Prior to the initial operation of the CompuScale III the following checks should be made:
» the test reference should be removed from the belt scale.
» the totalizer(s) should be reset to zero.
The CompuScale III is now ready for service.
Ensure the CompuScale III is in the RUN mode.
To enter the RUN mode,
The CompuScale III assumes the last RUN mode display accessed.
If necessary, to display Load.
Apply material to the running belt, ensuring the Design Load is not exceeded.
to display the current belt speed. Ensure the design Speed is maintained.
to display the current material rate. Ensure the design Rate is not exceeded.
to display the current material total. Observe the total value incrementing.
A program of calibration checks should be performed weekly at first. The frequency of these checks may be
reduced as time and experience dictate.
All personnel should be instructed on the safe and proper operation of the CompuScale III and be instructed
when and if a calibration check should be performed, what level of zero and span deviation is acceptable, and
when to reset the totalizer(s).
If desired, a photocopy of the following page may be provided to personnel responsible for CompuScale III
daily operation.
PL-367