PROGRAMMING CHART
PAR
NAME
VALUE
VALID RANGE (F or _ = factory setting)
P0
RATE UNITS
[
]
IMP: 1(T/h),2(LT/h),3(lb/h),4(lb/min) Metric: 1(t/h),2(kg/h),3(kg/min)
P1
RATE
[
]
0.0001 to 99999 (F = 0.000)
P2
LOCAL TOTAL
[
]
1,2,or 5 x .0001,.001,.01,.1,1,10,100,or 1000
P3
REMOTE TOTAL
[
]
1,2,or 5 x .0001,.001,.01,.1,1,10,100,or 1000
P4
BELT SPEED
[
]
0.0001 to 99999 (F = 0)
P5
SPEED CONSTANT
[
]
0.0001 to 99999 (F = 0 for variable speed, 100 for constant speed)
P6
BELT LENGTH
[
]
0.0001 to 99999 (F = 0)
P7
TEST REFERENCE
[
]
0.0001 to 99999 (F = 0)
P8
SPAN ADJUST
[
]
0 (off), 1 (% change), 2 (material test)
P9
FACTORING
[
]
0 (off), 1(factor test reference)
P10
LOW TOTAL CUTOFF
[
]
0.0 to 100.0 (F=3.00)
P11
RATE DISPLAY DAMPING
[
]
1 to 999
P12
LOAD DISPLAY DAMPING
[
]
1 to 999
P13
SPEED DISPLAY DAMPING
[
]
1 to 999
P14
RATE OUTPUT DAMPING
[
]
1 to 999
P15
RATE OUTPUT AVERAGE
[
]
0 to 99999
P16
RATE BAR GRAPH ASSIGNMENT [
]
0 (Rate Output P14), 1 (undamped Rate), 2 (Rate Display, P11)
P17
RATE OUTPUT MIN
[
]
0 to 4095 (F = 631)
P18
RATE OUTPUT MAX
[
]
0 to 4095 (F = 3160)
P19
SPEED ADJUST
[
]
0.0000 to 99999 (F = dynamic speed)
P20
TEST REFERENCE SELECT
[
]
0 (test weight), 1 (ECAL), 2 (test chain)
P21
SENSOR TYPE
[
]
0 (LVDT), 1 (1 load cell),2 (2 load cells), 4 (4 load cells), 8 (LCPA-08)
P22
ECAL ADJUST
[
]
0 (off), 1(on), 2(adjust), [ ] count
P26
MULTISPAN
[
]
0 to 8 (F = 0)
P30
CALIBRATION DURATION
[
]
0.1 to 99 (whole numbers only for P31 operation, F = 1)
P31
VERIFICATION TOTAL
[
]
0 (off), 1 (HOLD TOTAL), 2 (add to Total)
P32
VERIFICATION TOTAL RES
[
]
0 (same as P2), 1 (P2 x 1/10)
P40
BAUD RATE
[
]
300, 1200, 2400, 9600
P41
DATA TRANSMIT INTERVAL
[
]
0 to 99999 (F = 30)
P42
DATA MESSAGE
[
]
0 (off),1 (Rate),2 (Total),3 (Load),4 (Speed),5 (1,2,3,& 4),9 (System)
P43
SERIAL PRINTER
[
]
0 (off), 1 (on)
P51
RELAY 1
[
]
0 (off), 1 (Rate), 2 (Load), 3 (Speed), 4 (Fixed)
[ ] (hi) [ ] (lo) [ ] (deadband) in %
P52
RELAY 2
[
]
0 (off), 1 (Rate), 2 (Load), 3 (Speed), 4 (Fixed)
[ ] (hi) [ ] (lo) [ ] (deadband) in %
P55
100% TEST REFERENCE
[
]
0.0001 to 99999 (F = Rate (P1) / Speed (P4), display only)
P60
SOFTWARE REVISION
[
]
1.00 to 99.99 (display only)
P61
MEMORY TEST
[
]
Pass or Fail, (display only)
P63
TOTALIZER CONTACT DUR
[
]
0.025 TO 8.323 seconds (F = 1 until P1 and P3 are set)
P64
ZERO RECORD
[
]
(display only)
P65
SPAN RECORD
[
]
(display only)
P66
SECURITY LEVEL SELECT
[
]
0(off),1(P#’s),2(P#’s,Total),3(P#’s,Zero,Span),4(P#’s,Total,Zero,Span)
P70
CLOCK/CALENDAR
[
]
hrs(0-23),min(0-59),day(1-31),month(1-12),year(00-99)
P71
TIME
[
]
HH:MM, (24 hour format, display only)
P72
DATE
[
]
YY/MM/DD format (display only)
P77
INITIAL ZERO RESET
[
]
0 (off), 1 (reset)
P80
V/F CONVERTER OUTPUT
[
]
0 to 131,000 counts, (display only)
P81
LOAD CELL A INPUT
[
]
0.00 to 50.00 mV, (display only)
P82
LOAD CELL B INPUT
[
]
0.00 to 50.00 mV, (display only)
P83
LOAD CELL C INPUT
[
]
0.00 to 50.00 mV, (display only)
P84
LOAD CELL D INPUT
[
]
0.00 to 50.00 mV, (display only)
P85
V/F CONVERTER INPUT
[
]
-1.00 to 4.00 V, (display only)
P88
INITIAL SPAN RESET
[
]
0 (off), 1 (reset)
P90
MSI NUMBER
[
]
0 (non MSI), 1 to 4 (MSI from tail pulley)
P91
POS B L/C (A+B)
[
]
0 to 131,000 counts
P92
POS B L/C (B)
[
]
0 to 131,000 counts
P93
POS A L/C (B)
[
]
0 to 131,000 counts
P94
POS A L/C (A+B)
[
]
0 to 131,000 counts
P95
LOAD CELL BALANCE
[
]
0 to 131,000 counts
P99
RESET
[
]
0 (off), 1 (Partial), 2 (Master)
P100
PARAMETER LIST
[
]
0 to 99 in groups of 10, (display only)
PL-367