VERIFICATION TOTALIZER
Activates a secondary internal totalizer which totals the amount of material conveyed during the number of belt
revolutions set by P30. (The P30 value must be a whole number.) This feature may be used to verify
calibration accuracy from the RUN mode without stopping material flow.
The amount of material totalized by the verification totalizer may be included or excluded from the main totalizer
counts.
enter:
0 = verification totalizer off (F)
1 = do not totalize material during the verification.
2 = totalize material during the verification.
P32
VERIFICATION TOTALIZER RESOLUTION
Defines the amount of material weight to be measured, prior to initiating a verification totalizer update. The
weight portion of the Rate Unit (P0) is assumed.
enter:
0 = same as the Local Total (P2) value.(F)
1 = 1/10 of the Local Total (P2) value.
P40
BAUD RATE
Defines the baud rate for PORT 1 data message communication.
The baud rate must be set to the value required by the external device(s) connected to the PORT1 (TB1)
current loop or RS-232C communication connections.
enter:
300
1200
2400
9600 (F)
P41
DATA TRANSMIT INTERVAL
Defines the time lapse in minutes between unsolicited data message transmissions. Range = 0 to 99999
The Data Transmit Interval may be adjusted as required to control the level of message traffic between the
CompuScale III and the external device(s) connected to the PORT 1 and/or PORT 2 bipolar current loop or
RS-232C communications connections.
If a value greater than 50,000 is entered, the data message (P42) is transmitted only when the TB1- 35, 37
contacts are closed.
enter:
desired value, (F = 30)
PL-367
7 – 9