Turn Off welding power source, and
check voltage on input capacitors
according to Section 8-9 before
proceeding.
!
Installation must meet all National and
Local Codes
−
have only qualified per-
sons make this installation.
!
Disconnect and lockout/tagout input
power before connecting input
conductors from unit. Follow estab-
lished procedures regarding the in-
stallation and removal of lockout/
tagout devices.
!
Make input power connections to the
welding power source first.
!
Always connect green or green/yellow
conductor to supply grounding
terminal first, and never to a line
terminal.
NOTICE
−
The Auto-Line circuitry in this unit
automatically adapts the power source to the
primary voltage being applied. Check input
voltage available at site. This unit can be con-
nected to any input power between 208 and
575 VAC without removing cover to relink the
power source.
See rating label on unit and check input volt-
age available at site.
1
Input Power Conductors (Customer
Supplied Cord)
Select size and length of conductors using
Section 4-6. Conductors must comply with
national, state, and local electrical codes. If
applicable, use lugs of proper amperage
capacity and correct hole size.
Welding Power Source Input Power
Connections
2
Strain Relief
Install strain relief of proper size for unit and
input conductors. Route conductors (cord)
through strain relief and tighten screws.
3
Welding Power Source Grounding
Terminal
4
Green Or Green/Yellow Grounding
Conductor
Route green or green/yellow grounding con-
ductor through current transducer and con-
nect to welding power source grounding ter-
minal first.
5
Welding Power Source Line Terminals
6
Input Conductors L1, L2, L3
Connect input conductors L1, L2, and L3 to
welding power source line terminals.
Reinstall side panel on welding power source.
Disconnect Device Input Power
Connections
7
Disconnect Device (switch shown in the
OFF position)
8
Disconnect Device Grounding Terminal
9
Disconnect Device Line Terminals
Connect green or green/yellow grounding
conductor to disconnect device grounding ter-
minal first.
Connect input conductors L1, L2, and L3 to
disconnect device line terminals.
10 Over-Current Protection
Select type and size of over-current protec-
tion using Section 4-6 (fused disconnect
switch shown).
Close and secure door on disconnect device.
Follow established lockout/tagout procedures
to put unit in service.
8-10. Connecting 3-Phase Input Power (Continued)
Notes
Work like a Pro!
Pros weld and cut
safely. Read the
safety rules at
the beginning
of this manual.
Summary of Contents for Axcess E 300
Page 14: ...OM 244 814 Page 10 ...
Page 18: ...OM 244 814 Page 14 Notes ...
Page 22: ...OM 244 814 Page 18 Notes ...
Page 26: ...OM 244 814 Page 22 Notes ...
Page 30: ...OM 244 814 Page 26 Notes ...
Page 56: ...OM 244 814 Page 52 Notes ...
Page 63: ...Trouble OM 244 814 Page 59 Notes ...
Page 68: ...OM 244 814 Page 64 Figure 14 2 Circuit Diagram For Axcess E 300 2 Of 2 ...
Page 69: ...Circuits OM 244 814 Page 65 248 763 E Part 2 Of 2 ...
Page 70: ...OM 244 814 Page 66 Figure 14 3 Circuit Diagram For Axcess E 450 1 Of 2 ...
Page 71: ...Circuits OM 244 814 Page 67 245 131 F Part 1 Of 2 ...
Page 72: ...OM 244 814 Page 68 Figure 14 4 Circuit Diagram For Axcess E 450 2 Of 2 ...
Page 73: ...Circuits OM 244 814 Page 69 245 131 F Part 2 Of 2 ...
Page 74: ...OM 244 814 Page 70 Figure 14 5 Circuit Diagram For Axcess E 675 1 Of 2 ...
Page 75: ...Circuits OM 244 814 Page 71 250 570 C Part 1 Of 2 ...
Page 76: ...OM 244 814 Page 72 Figure 14 6 Circuit Diagram For Axcess E 675 2 Of 2 ...
Page 77: ...Circuits OM 244 814 Page 73 250 570 C Part 2 Of 2 ...
Page 78: ...OM 244 814 Page 74 Figure 14 7 Circuit Diagram For Axcess E Module ...
Page 79: ...Circuits OM 244 814 Page 75 250 571 C ...
Page 80: ...OM 244 814 Page 76 Notes ...
Page 106: ...Notes ...