OM-4421 Page 62
12-3. Grounding When Supplying Building Systems
ST-800 576-B
1
Equipment Grounding
Terminal
2
Grounding Cable
Use #10 AWG or larger insulated
copper wire.
3
Ground Device
Use ground device as stated in
electrical codes.
!
Ground generator to system
earth ground if supplying
power to a premises (home,
shop, farm) wiring system.
!
Also see AWS Safety &
Health Fact Sheet No. 29,
Grounding of Portable And
Vehicle Mounted Welding
Generators.
GND/PE
1
2
2
3
12-4. How Much Power Does Equipment Require?
S-0623
1
Resistive Load
A light bulb is a resistive load and
requires a constant amount of power.
2
Non-Resistive Load
Equipment with a motor is a non-re-
sistive load and requires approxi-
mately six times more power while
starting the motor than when running
(see Section 12-8).
3
Rating Data
Rating shows volts and amperes, or
watts required to run equipment.
Amperes x Volts = Watts
Example 1:
If a drill uses 4.5 am-
peres at 115 volts, calculate its run-
ning power requirement in watts.
4.5 A x 115 V = 520 W
The load applied by the drill is 520
watts.
Example 2:
If three 200 watt flood
lamps are used with the drill from Ex-
ample 1, add the individual loads to
calculate total load.
(3 x 200W) + 520 W = 1120 W
The total load applied by the three
flood lamps and drill is 1120 watts.
VOLTS 115
4.5
60
AMPS
Hz
1
2
3
3
Summary of Contents for 500 X
Page 35: ...OM 4421 Page 29 Notes ...
Page 39: ...OM 4421 Page 33 Notes ...
Page 47: ...OM 4421 Page 41 SECTION 9 MAINTENANCE TROUBLESHOOTING 9 1 Maintenance Label ...
Page 59: ...OM 4421 Page 53 Notes Welding Symbols Ref AWS ANSI A2 4 ...
Page 61: ...OM 4421 Page 55 223 522 B ...
Page 62: ...OM 4421 Page 56 Figure 10 2 Circuit Diagram For CC CV Welding Generator ...
Page 63: ...OM 4421 Page 57 223 523 B ...
Page 94: ......