![Milestone PrestoCHILL Operator'S Manual Download Page 27](http://html1.mh-extra.com/html/milestone/prestochill/prestochill_operators-manual_1795354027.webp)
PrestoCHILL
MM138-003
– Operator Manual
27
When in manual mode, press the
“Start defrost”
icon on main screen to start defrost procedure. At the end
of this procedure the plate returns to room temperature.
In automatic mode, defrost start is already set and it will not need to be initiated by the operator.
3.9.1. HEPA12 Filter
For safety reasons, between the working area and the defrost pump, there is a HEPA12 filter that filters
possibly dangerous pathogens in the vapors.
This filter must be changed after the defrost pump has worked for 250 hours.
The software advises you tha
t the filter life is finished with the message “Filter needs to be replaced. Please
do it”, at the starting of the first freezing program of the day.
Change the HEPA12 filter following the instructions in the chapter 4.4.1 How to change the HEPA12 filter.
Check the cool trap daily. If needed, empty it. Refer to chapter MAINTENANCE 4.3.
It is strongly suggested to do a defrost cycle once a day.
Defrost settings are under Service settings, accessible only to Service personnel.
Contact
for further information.
The preset defrost temperature is 30°C, but during the cycle higher temperature values
can be reached.
Avoiding HEPA12 filter change, can be dangerous for operator safety.
To change the filter, refer to chapter 4.4.1.
Summary of Contents for PrestoCHILL
Page 1: ...PrestoCHILL Flash Chiller for Frozen Sections OperatorManual MM138 ...
Page 2: ......
Page 71: ......