TECHNICAL DATA

1. Current and Time Adjustments

         

Earth-fault Low-set Current (l>) Adjustment

            • This adjustment is for setting the minimum earth-fault current for tripping. If the 

              measured current exceeds this threshold value, tripping starts. After a prefixed

              delay time determined by the DELAY adjustment, the trip contacts will be activated.
            • The setting range is from 0.1A to 2A.

          

Earth-fault High-set Current (l>>) Adjustment

            • This adjustment is for setting the instantaneous tripping current due to an earth-fault.
            • The setting range is from 1x to 10x of the earth-fault low-set setting value.

 

 

        l>> = a x l>,          a = 1 to 10 

            • This high-set feature can be disabled by setting the tripping current to infinity (  

'

 )

     
          

Time Delay (DELAY) Adjustment

            • This time delay setting is for setting the delay time from the start of the earth-fault 

               low-set tripping to actual tripping of the relay contact. 
            • The setting range is from 0.05 sec to 1.0 sec.

2. Light Indicators

           

The light indicators display the status of the system.

 

 

Indicator 

 

  AUX        l>         l>>                                 Status
   Off 

    Off         Off      No auxiliary power supply.

   On 

    Off         Off      System normal mode. No tripping.

 

 

      

 

 

   On          On             Off

 

    Earth-fault low-set start.

   On

 

  Blink

 

       Off

 

    Earth-fault low-set tripped.

  

   On          Off             On     Earth-fault high-set start.
   On

   Off           Blink     Earth-fault high-set tripped.