background image

 

Faults, causes and remedies 

 
The troubleshooting must only be carried out by a qualified specialist, and 
work on the electrical connection must only be carried out by a qualified 
electrician. 

 

Faults

 

Causes

 

Remedy

 

Pump is not 

running although 

the power supply 

is switched on 

Electrical fuse 

defective

 

Check fuses

 

No voltage supply 

at pump

 

Rectify the power 

interruption

 

Noisy pump

 

Cavitation due to 

insufficient suction 

pressure 

Increase the system 

pressure within the 

permissible range 

Check the delivery head 

and set it to a lower 

head if necessary 

Building does not 

warm up 

Thermal output of 

the heating 

surfaces is too low 

Increase setpoint

 

Change the control 

mode from  

Δp-c to Δp-v

 

 

Fault signals

 

 The fault signal LED indicates a fault. 

 The pump switches off (depending on the fault) an attempts a cyclical 

restart. 

 

LED

 

Faults

 

Causes

 

Remedy

 

Lights up 

red 

Blocking

 

Rotor blocked

 

Activate 

manual 

restart or 

contact  

customer 

service 

Contacting/ 

winding 

Winding defective

 

Flashes 

red 

Under/overvoltage

 

Power supply too  

low/high on mains 

side 

Check mains 

voltage and 

operating 

conditions, 

and request 

customer 

service 

Excessive 

module 

temperature 

Module interior too 

warm 

Short-circuit

 

Motor current too 

high 

Flashes 

red/ 

green 

Generator 

operation 

Water is flowing 

through the pump 

hydraulics, but there 

is no mains voltage 

at the pump 

Check the 

mains 

voltage, 

water 

quantity/pre

ssure and 

the ambient 

conditions 

Dry run

 

Air in the pump

 

Overload

 

Sluggish motor, 

pump is operated 

outside of its 

specifications (e.g. 

high module 

temperature). The 

speed is lower than 

during normal 

operation. 

 

Activating factory setting 

 

The factory setting is activated by pressing and holding the operating 
button whilst switching off the pump. 

  Press and hold the operating button for atleast 4 seconds. 

  All LEDs flash for 1 second. 

  The LEDs for the last setting flash for 1 second. 

 

Decommissioning

 

Shutting down the pump 
 

Shut  down  the  pump  immediately  if  the  connecting  cable  or  other 
electrical components are damaged.  

  Disconnect the pump from the power supply.  

  Contact a service technician

 

 
 
 
 

 

Maintenance

 

Cleaning 

 

 

Carefully remove dirt from the pump on a regular basis using a dry 
duster. 

 

Never use liquids or aggressive cleaning agents.

 

 

Manual restart 

 

  The  pump  attempts  an  automatic  restart 

upon detecting a blockage. 
If the pump does not restart automatically: 

  Activate  manual  restart  via  the  operating 

button:  press  and  hold  for  5  seconds,  then 
release. 

-

  The  restart  function  is  initiated,  and  lasts 

max. 10 minutes. 

-

  The LEDs flash in succession clockwise. 

  To  cancel,  press  and  hold  the  operating 

button for 5 seconds. 

If the fault cannot be remedied, contact an 
authorized service center.

 

 

 

NOTICE 

After the restart, the LED display shows the previously 
set values of the pump. 

 

 

Venting 

 

  Fill and vent the system correctly.  

If the pump does not vent automatically: 

  Activate  the  pump  venting  function  via the 

operating button:  
Press and hold for 3 seconds, then release. 
The pump venting function is initiated and lasts 
10 minutes. 
The top and bottom LED rows flash in turn at 
1 second intervals. 

  To  cancel,  press  and  hold  the  operating 

button for 3 seconds. 

 
 
 
 

 

NOTICE 

After venting, the LED display shows the previously set 
values of the pump. 

 

 

Lock/unlock the button 
 

  To activate the key lock, press and hold the 

operating button for 8 seconds until the LEDs 
for  the  selected  setting  briefly  flash,  then 
release. 

-

  LEDs flash constantly at 1-second intervals. 

-

  The key lock is activated: pump settings can 

no longer be changed. 

  The  key  lock  is  deactivated  in  the  same 

manner as it is activated. 

 
 
 

 

NOTICE

 

All  settings/displays  are  retained  if  the  power  supply  is 
interrupted. 

 

 
 
 
 
 

 

Instruction for projecting 

 

Summary of Contents for eCompact Plus 12kW

Page 1: ...Guidebook for installation handling and maintenance ENG eCompact Plus Electric block boiler for heating systems with thermoregulatory microprocessor FG eCompactPlus 01 2020...

Page 2: ...on air emission 5 Electrical connection 5 1 Positions of introducer for the introduction of the power cable 5 2 Connecting power voltage cable 5 3 Scheme for connecting power voltage cable 5 4 Connect...

Page 3: ...assembly All electric works should be performed by authorised person in accordance with corresponding regulations Commissioning and maintenance and repairs should be done by authorised service only Te...

Page 4: ...o spare parts not delivered by the manufacturer Use only original spare parts Material damages due to freezing When there is damage due to freezing drain water from the boiler tank and pipelines for h...

Page 5: ...ax pressure of 2 6bar which should be controlled on regular basis Boiler should be handled only by adults who are familiar with instructions and work of the boiler Do not close safety valve Inflammato...

Page 6: ...lyurethane polystyrene polyethylene floor fibre materials Table 2 Ignitable materials and composition of elements according to DIN 4102 2 8 Product description Basic components of boiler Boiler body D...

Page 7: ...nt 11 Automatic fuses with voltage trigger 12 Terminal for room thermostat 13 Microprocessor plate 14 Heater relay 9 18kW contactor 24 27kW 15 Temperature sensor 16 Safety thermostat STB 17 Control pa...

Page 8: ...is damaged during delivery Check if delivery is complete Part Pieces Boiler eCompact Plus 1 Assembly Set 1 Instructions for handling 1 2 11 Factory plate Factory data plate is placed on the external...

Page 9: ...2 12 Dimensions and technical data 2 12 1 Dimensions and technical data for boiler Image 2 Dimensions and connection Device data...

Page 10: ...cable cross section for three phase power supply mm 5 2 5 5 2 5 5 4 5 4 5 6 5 6 Needed fuses for single phase supply voltage A 1 32 1 50 Minimum cable cross section for single phase power supply mm 3...

Page 11: ...carts for bags with tighten strip The product should be in horizontal position during transportation Avoid shocks or collisions Packed boiler put on carts for bags if needed secure it with strip and...

Page 12: ...ulations and local laws Electric connector should be done according to the connecting plans After corresponding installation of device execute grounding of the plant Before opening device and all work...

Page 13: ...dowel enclosed in device packaging or adequate dowel for unusual kind of wall Then screw bolts into delivered dowels or other in such way that are left out from the wall min 5 mm max 10mm Carefully ha...

Page 14: ...shines near the mark bar 4 7 1 Filling the boiler with heating water and sealing test Waterproof should be tested prior to put on the boiler 1 Check pre pressure of expansion dish If is pressure leve...

Page 15: ...set is on lower side below of device They are on lower plate of device in the back left corner image 6 It is intended for connecting device when power cable comes from the lower side of the boiler II...

Page 16: ...nnected to three pole fusses L1 L2 and L3 When introducing a power cable into the boiler through any selected set of glands carefully patch the cable to the three pole automatic fuses to avoid damagin...

Page 17: ...of digital programmable room thermostat with battery supply Image 9 Scheme of boiler connecting on three phase power supply Image 8 Scheme of boiler connecting to single phase power supply ONLY FOR P...

Page 18: ...boiler of 12 18kW 3 2667W for boiler of 24kW 3 3000W for boiler of 27kW G3 Heater 3 2000W for boiler of 18kW 3 2667W for boiler of 24kW 3 3000W for boiler of 27kW LCTR 2 Microprocessor thermoregulato...

Page 19: ...Electric connecting Image 12 Boiler electric scheme eCompact Plus with nominal power of 6kW...

Page 20: ...Electric connecting Image 13 Boiler electric scheme eCompact Plus with nominal power of 9kW and 12kW...

Page 21: ...Electric connecting Image 14 Boiler electric scheme eCompact Plus with nominal power of 18kW 24kW and 27kW...

Page 22: ...on Prior to turn on check if heating installation is filled with water and air vent Turn on main switcher below device Heating system and device parameters will appear on display Device is adjusted by...

Page 23: ...l 7 2 2 Basic adjustments The current temperature is continuously displayed on the display indicating the LED that is lit beside the Temp mark To display other parameters use the keys and In addition...

Page 24: ...Each touch to the button will increase decrease given temperature of the boiler for 1 C Working temperature range is 10 C 80 C Confirmation of change must be done by pressing button SET If change is...

Page 25: ...urns off all heaters and pump delayed for 2 min and pressure measuring indicator starts to flash quickly Display still shows present temperature of the boiler image 19 It is necessary to reduce pressu...

Page 26: ...ays for 2 min and temperature measuring indicator will flash quickly image 22 With this temperature value there is danger of freezing and boiler damage so the work of this device will be blocked To co...

Page 27: ...T 100 C display of its value is not possible to see on the screen so in this will appear code EH meaning that temperature is T 100 C image 26 Measuring temperature indicator will continue to flash qui...

Page 28: ...g T 2 C or upper limit T 89 C of temperature of the heating system Measure Turn off electric power supply for the boiler Call service Graphic display of the area of blockade of the boiler work conditi...

Page 29: ...manufacturer instructions 7 3 8 Heating discontinuity With short time discontinuity of heating working regime the boiler temperature must be decreased using thermo regulator of the boiler To prevent...

Page 30: ...elivered by the manufacturer Control examination log is provided on chapter 8 4 Perform works in accordance with log on control and maintenance All deficiencies remove immediately 8 1 Boiler cleaning...

Page 31: ...heck if there is any damage on electric duct lines 6 Check if electric control connections and used elements are fitted tighten it if needed 7 Check thermo regulator on boiler 8 Check function of safe...

Page 32: ...economy concepts we use only the best technique and materials Packaging Regarding packaging we respect system of recycling which is specific in certain states and which secure optimal recycling All m...

Page 33: ...amaged Check all three phases Check set power of boiler Change damaged part Change damaged part Boiler heats but it is very noisy Higher level of noise during work Air in the system Small water flow P...

Page 34: ...lector Button settings 9 Drain faucet Wilo Para MSL 6 43 SC is a circulating pump for heating systems heating systems for family houses and other similar systems The most important characteristics of...

Page 35: ...ess and hold the operating button for atleast 4 seconds All LEDs flash for 1 second The LEDs for the last setting flash for 1 second Decommissioning Shutting down the pump Shut down the pump immediate...

Page 36: ...precautions for assembly installation and maintenance are described in the operating and installation instructions Read and follow the operating and installation instructions 10 All of the data that...

Page 37: ...Note...

Page 38: ...cted by intellectual property of MIKOTERM d o o Any unauthorized use copying or publication in whole or in part by other entities without the authorization of MIKOTERM d o o is punishable by law Nis 2...

Reviews: