5.4 Working parts

Working parts are components which are degenerated during prescribed application and as expected have to renewed
during the service live of the fan.
Special data see delivery note, Fan Identity Card or label of motor (if necessary ask for information).

Working parts VRE - W  

(direct driven):

Working part is the motor (renew securing elements of hub connection and hub protection cap).
Special data see delivery note, Fan Identity Card or label of motor.

Working parts VRE - R  

(belt driven):

Motor

Belt

Tensioner:

tensioner
Pulley (with axle an bearings)

Flange bearing / block bearing

bearings with lubrication nipples

Grease type (unless otherwise specified ):

SHELL Alvania R3, (ARAL Aralub HL 2, ESSO Beacon 2)
amount of grease: 10 ... 20 g per bearing

Lubrication interval (orientation for normal use)

Special design GD 

(gastight casing)

Working part is the sealing ring. It is recommended to renew the sealing ring if the bearing or motor will be exchanged.

6. Waste removal

MIETZSCH-made fans are long-lived products. Consequently, waste removal is a problem occurring not earlier than
many years after starting.
According to present legal prescriptions, the single components are not regarded as hazardous waste.

Š

Metal components (base, motor, screws etc.) are scrapped as usual.

Š

Plastic components have to be cleaned and can then be treated as normal waste.

Residual materials and deposits in the fan have to be removed by the user in consideration of conditions of environment
control.

7

Speed of impeller / rpm

1000

2000

3000

4000

5000

VRE 100 ... 160

12000

10000

10000

8000

7000

VRE 200 ... 250

12000

10000

9000

6000

6000

VRE 315 ... 630

10000

8000

7000

5000

-

VRE 710 ... 1000

10000

8000

-

-

-

nenngröße

Fan size

OI-VRE 05/02

Summary of Contents for VRE-W Series

Page 1: ...nt 3 2 Integrating the fan into the plant 3 3 Initial starting 4 Operation and maintenance 5 Repair instructions 5 1 Cleaning 5 2 VRE W direct driven fans 5 3 VRE R belt driven fans 5 3 1 Replacing th...

Page 2: ...pplied plastics to the conveying medium has to be tested EX type fans require the ignition temperature and area of explosion risk to be considered Standard fans with EX type motors have no general exp...

Page 3: ...e rooms Persons in such rooms must be protected by suitable measures from injuries by noise 2 Transportation and storage Loading work has to be carried through by experienced persons only Use hoisting...

Page 4: ...nity of the fan must be blocked to exclude danger to persons life and limb and material values in the case of a possible destruction by transportation damages or foreign bodies Proceed in the same way...

Page 5: ...has been switched off Make sure that it cannot be switched on during repair work After repair proceed as in initial starting Section 3 3 5 1 Cleaning For cleaning the fan inside use the cleaning open...

Page 6: ...rrect belt tension after running time of 30 to 60 minutes with full load Changes of the belt drive such as variation of transmission ratios are permissible only after consultation with the MIETZSCH co...

Page 7: ...Lubrication interval orientation for normal use Special design GD gastight casing Working part is the sealing ring It is recommended to renew the sealing ring if the bearing or motor will be exchange...

Page 8: ...Gesch ftsf hrer Dresden den 16 06 2003 D MIETZSCH GmbH Lufttechnik Dresden Gro enhainer Str 137 01129 Dresden Fax 0351 8 58 00 74 http www mietzsch de konf_vre EG Konformit tserkl rung EC Declaration...

Reviews: