Calculation example
A
Wall pipe, with louvred vent
= 1 x 12' 6" (3.8 m)
Additional duct length
= 12' 6" (3.8 m)
B/D 2 bends, 90° plastic piping
= 2 x 2' 7 1/2" (0.8 m)
Additional duct length
= 5' 3" (1.6 m)
C
0.5 m plastic piping
= 0.5 x 3' 3" (1 m)
Additional duct length
= 1' 8" (0.5 m)
Total duct length
= 19' 5" (5.9 m)
Result: A duct diameter of 4" (100 mm)
is adequate as the total duct length is
less than the 66' (20 m) specified in
Table II.
Dimensions for exhaust
connection
View from above
Rear view of the dryer
Installation - extraction ducting
89