NOTE 

Remark per EMC Directive 89/336/EEC 
 
For to prevent flicker impressions during the start of the 
compressor  (technical process), following    installation   condi-
tions apply. 
 
The power connection for the air conditioner has to be done 
at the main power distribution.The distribution has  to be of 
a low impedance, normally  the required impedance reaches 
at a 32A fusing point. 
 
No other equipment has to be connected with this power 
line. 
 
For detailed  installation acceptance,  please refer to your 
contract with the power supplier if  restrictions do apply for 
products  like  washing  machines, air conditioners  or  
electrical ovens. 
 

 

 

 

installation manual 

Please  refer  to  the  following  figure  for    the   distance  
measurement between the screw bolts. 
 
Please install with screw bolts. 
 
The handling to the ceiling varies from the constructions, consult 
the construction personnels for the specific procedures. 
 
The  size  of   the ceiling to  be handled

.

Do keep the ceiling flat. Con-

solidate the roof beam for possible vibration. 
 
Cut off the roof beam. 
 
Strengthen the place cut off, and consolidate the roof beam. 
 
Carry  out  the  pipe  and  line  operation  in the ceiling after 
finishing the installation of the main body.  While choosing where 
to start the operation, determine the direction of the pipes to  be 
drawn out. Especially in case there is a ceiling, position the 
refrigerant pipes, drain pipes, indoor & outdoor lines to the connec-
tion places before hanging up the machine. 
 
The installation of hanging screw bolts. 
 

 

 

 

Fig.4-1 

   

Hanging screw bolts 

Ceiling  

Timber over the beam 

Roof beam 

Put the square timber traversely overthe roof beam, then 
install the hanging screw bolts. (Refer to 

Fig.4-1

)  

Wooden construction 

New concrete bricks 

Fig.4-2 

Inlaying or embedding the screw bolts (Refer to 

Fig.4-2

)

   

Blade shape insertion 

Slide insertion 

Installing 

Φ

10 Hanging Screw Bolts (4 Bolts) 

4.   INDOOR UNIT INSTALLATION 

Cautions on remote controller installation 
 
Never throw or beat the controller. 
 
Before installation,  operate the remote controller to determine 
its location in a reception range. 
 
Keep the remote controller at least 1m apart from the  nearest  
TV  set  or  stereo  equipment.  (It  is necessary   to  prevent   
image   disturbances   or noise interferences.) 
 
Do  not  install  the  remote  controller  in  a  place exposed  to  
direct  sunlight  or  close to a heatingsource, such as a stove. 
Note  that  the  positive  and  negative  poles  are  in  right positions 
when loading batteries. 

 

 

 

 

1. Remote controller....................................1 

2. Remote controller holder.........................1 

3. Mounting screw 

   (ST2.9x10-C-H)........................................2 

4. Alkaline dry battery(AM4) 

   ..................................................................2 

Remote controller & Its Frame 

For power details of the air conditioner, refer to the rating 
plate of the product. 
 
For any question contact your local dealer.  

 

 

Table.3-1 

 Name of  
Accessories 

Installation manual

KJR-10B Wire  
controller 

Pipe insula- 
tion material 

Adhesive tape for seal 

Heat insulation 

To connect drain pipe 

Q‘ty  

(This manual) 

Outline 

Usage 

Wire

 control the  

air-conditioner 

Clasp 

Network matching wire 

Water outlet joint 

For drainage 

Chucking the joint which 
 connect the drain hose  
and the outlet of indoor  
unit 

The indoor unit which at 
the terminal of  
communication system  
shouldconnect a  
impedance between port 
P and port Q 

The following are selectable accessories 

3.  ACCESSORIES 

7.1-16.0

20.0-28.0

Remote controller 

holder 

Mounting screw  

Fig.3-1 

Remote 
controller 

Summary of Contents for Split Duct Air Conditioner

Page 1: ...DC AC Inverter Commercial Air conditioner The Digital Scroll and DC AC Inverter share the same indoor units Thank you very much for purchasing our air conditioner Before using your air conditioner pl...

Page 2: ...es or malfunction may be caused if unavoidable please consult the professionals There is mineral oil like the oil of cutting machine There is much salty air Near the coast There is caustic gas such as...

Page 3: ...er traversely overthe roof beam then install the hanging screw bolts Refer to Fig 4 1 Wooden construction New concrete bricks Fig 4 2 Inlaying or embedding the screw bolts Refer to Fig 4 2 Blade shape...

Page 4: ...The static pressure outside the unit is 200Pa the length of the air pipe attached is determined by this parameter The positioning of ceiling hole and indoor unit and hanging screw bolts Routine method...

Page 5: ...36 69 90 15 50 800 1148 137 125 11 28 169 691 52 35 136 123 179 15 ELECTRICAL CONTROL BOX PLASTIC COVER 930 135 88 24 46 68 82 82 56 270 420 249 29 722 65 75 61 43 189 123 642 420 85 856 214 86 800 44...

Page 6: ...1 The whole unit status show as Fig 4 11 2 Remove the all 11 screw from fixed Safety Drain Tray and then take off the tray as figure showed in Fig 5 11 3 Take off the tray along the direction of the a...

Page 7: ...3 Refer to Fig 4 13 remove all 4 bolts from fan assembly see Fig 4 14 according to which orders to take off the fan assembly 4 Refer to Fig 4 14 horizontal pushing the fan assembly until it cannot not...

Page 8: ...ty Drain Tray and then take off the tray as figure showed in Fig 4 16 3 Take off the tray along the direction of the arrow show in Fig 4 16 4 Clean the tray and evaporator 5 Re install the unit follow...

Page 9: ...fan assembly see Fig 4 18 according to which orders to take off the fan assembly 3 Refer to Fig 4 18 horizontal pushing the fan assembly until it cannot not move any further and then lift up slightly...

Page 10: ...pipe Air intake Air outlet Refrigerant pipe flared connection 16 5 8 Refrigerant pipe flared connection 9 52 3 8 Air outlet duct flange 4 12 25 oblong suspention bolt holes Electrical parts box Entran...

Page 11: ...he direction of B and C divided the part B and part C of indoor unit The part A and part B of indoor unit individual put into the positionsite then install the indoor unit following the reverse order...

Page 12: ...0 300 2000 Q m3 h 5000 5500 6000 220 200 180 160 140 120 100 80 60 40 20 0 2500 3000 3500 4000 4500 P Pa 20KW h 50hz 25KW h 50hz Low speed Midium speed High speed Fig 7 2 240 260 280 300 2000 Q m3 h 5...

Page 13: ...ium speed High speed 2600 240 260 280 300 800 Q m3 h 2000 2200 2400 220 200 180 160 140 120 100 80 60 40 20 0 1000 1200 1400 1600 1800 P Pa 9 0KW h 60Hz 11 2KW h 60Hz Low speed Midium speed High speed...

Page 14: ...es fall in the pipe system during the time of installation The connecting pipe should not be installed until the indoor and outdoor units have been fixed already Keep the connecting pipe dry and do no...

Page 15: ...e by condensation Pass the bound connecting pipe through the wall conduit from outside Be careful of the pipe all ocation to do no damage to the tubing Connect the pipes Then open the stem of stop val...

Page 16: ...he air comes in the sound of the pump changes and the indicator of compound meter turns below zero Then fasten the nut When the pumping has finished close the Lo lever of the manifold valve completely...

Page 17: ...rs The wiring of 71T1 to 160T1 indoor unit please refer to Fig 11 1 and Fig 11 2 is the communication wiring for 200T1 250T1 and 280T1 indoor unit The reserved function is indicated in broken line tab...

Page 18: ...1234 SW1 ON 1234 1 means factory test mode 0 means auto addressing mode default setting 1 means DC fan is chosen 0 means AC fan is chosen 00 means DC fanstatic pressure is 0 reserved reserve d J1 J2...

Page 19: ...r unit communication is abnormal Condenser sensor check point is abnormal or outdoor temp sensor is abnomal Water level switch is abnormal Mode conflict Run lamp flashes at 2 5Hz The timer lamp flashe...

Page 20: ...r conditioner is pre heated by turning on the power 19 Low pressure pipe Hi pressure pipe Electric throttle part Liquid branch pipe 9 5 9 5 15 9 15 9 Gas branch pipe 10m 25 4 12 7 Accordingto theuser...

Reviews: