background image

Check all the joints with the leak detector or soap water. (See 

Fig.9-6

 as a reference illustration) 

 
       

Be sure to with insulating materials cover all the exposed parts 
of the flare pipe joints and refrigerant pipe on the liquid-side and 
the gas-side. Ensure that there is no gap between them. 
 
Incomplete insulation may cause water condensation. 
 
       
 

9.2   Check The Leakage 

9.3   Insulation 

B A 

Check-point of indoor unit 

Check-point of outdoor unit 

 
            A. Lo-stop valve            B. Hi-stop valve 
            C,D. Joints of the connecting pipe to the indoor unit. 

Fig.9-2 

9.   REFRIGERANT PIPE CONNECTION 

9.1  Expel The Air 

Bend the pipe with thumb 

Make the ends 
straight 

Fig.9-1 

Fig.8-3 

Fig.8-2 

Locate The Pipe 
 
Drill a hole in the wall (suitable just for the size of the wall conduit, 
90mm in general), then set on the fittings such as the wall conduit 
and its cover. 
 
Bind the connecting pipe and the cables together tightly with 
binding tapes. Do  not let air  in, which will cause water leakage 
by condensation. 
 
Pass the bound connecting pipe through the wall conduit from 
outside.  Be careful of the pipe all ocation to do no damage to the 
tubing. 
 
Connect the pipes. 
 
Then, open  the stem of stop valves of the outdoor unit to make 
the  refrigerant  pipe connecting the indoor unit with the outdoor 
unit fluently flow. 
 
Be sure of no leakage by checking it with leak detector or soap  
water. 
 
Cover the joint of the connecting pipe to the indoor unit with the 
sound proof/insulating sheath  (fittings),  and bind it well with the 
tapes to prevent leakage. 
 
 

 

 

 

 

 

Flaring 
 
Cut a pipe with a pipe cutter. 
 
Insert a flare nut into a pipe and flare the pipe. 
 

90 

lean crude burr 

Then expose the pipe(cover it with tapes after bending). 
 
To prevent collapsing of deforming, please bend the pipe at its 
biggest radius. 
 
Use bender to get a small radius pipes. 
 
Use the market brass pipe. 
Be sure to use the same insulating materials when you buy the 
brass pipe. (More than 9mm thick)  

 

Use frozen oil 

Fig.8-1 

 

 

14 

installation manual 

90+4 

_  

45+2 

_  

Outside diameter 

A(mm) 

Max 

8.7 

Φ

6.4mm 

Φ

9.5mm 

Φ

12.7mm 

Φ

15.9mm 

Φ

19.1mm 

12.4 

15.8 

19.0 

23.3 

8.3 

12.0 

15.4 

18.6 

22.9 

Min 

Table.9-1 

Fig.9-3 

Fig.9-4 

Summary of Contents for Split Duct Air Conditioner

Page 1: ...DC AC Inverter Commercial Air conditioner The Digital Scroll and DC AC Inverter share the same indoor units Thank you very much for purchasing our air conditioner Before using your air conditioner pl...

Page 2: ...es or malfunction may be caused if unavoidable please consult the professionals There is mineral oil like the oil of cutting machine There is much salty air Near the coast There is caustic gas such as...

Page 3: ...er traversely overthe roof beam then install the hanging screw bolts Refer to Fig 4 1 Wooden construction New concrete bricks Fig 4 2 Inlaying or embedding the screw bolts Refer to Fig 4 2 Blade shape...

Page 4: ...The static pressure outside the unit is 200Pa the length of the air pipe attached is determined by this parameter The positioning of ceiling hole and indoor unit and hanging screw bolts Routine method...

Page 5: ...36 69 90 15 50 800 1148 137 125 11 28 169 691 52 35 136 123 179 15 ELECTRICAL CONTROL BOX PLASTIC COVER 930 135 88 24 46 68 82 82 56 270 420 249 29 722 65 75 61 43 189 123 642 420 85 856 214 86 800 44...

Page 6: ...1 The whole unit status show as Fig 4 11 2 Remove the all 11 screw from fixed Safety Drain Tray and then take off the tray as figure showed in Fig 5 11 3 Take off the tray along the direction of the a...

Page 7: ...3 Refer to Fig 4 13 remove all 4 bolts from fan assembly see Fig 4 14 according to which orders to take off the fan assembly 4 Refer to Fig 4 14 horizontal pushing the fan assembly until it cannot not...

Page 8: ...ty Drain Tray and then take off the tray as figure showed in Fig 4 16 3 Take off the tray along the direction of the arrow show in Fig 4 16 4 Clean the tray and evaporator 5 Re install the unit follow...

Page 9: ...fan assembly see Fig 4 18 according to which orders to take off the fan assembly 3 Refer to Fig 4 18 horizontal pushing the fan assembly until it cannot not move any further and then lift up slightly...

Page 10: ...pipe Air intake Air outlet Refrigerant pipe flared connection 16 5 8 Refrigerant pipe flared connection 9 52 3 8 Air outlet duct flange 4 12 25 oblong suspention bolt holes Electrical parts box Entran...

Page 11: ...he direction of B and C divided the part B and part C of indoor unit The part A and part B of indoor unit individual put into the positionsite then install the indoor unit following the reverse order...

Page 12: ...0 300 2000 Q m3 h 5000 5500 6000 220 200 180 160 140 120 100 80 60 40 20 0 2500 3000 3500 4000 4500 P Pa 20KW h 50hz 25KW h 50hz Low speed Midium speed High speed Fig 7 2 240 260 280 300 2000 Q m3 h 5...

Page 13: ...ium speed High speed 2600 240 260 280 300 800 Q m3 h 2000 2200 2400 220 200 180 160 140 120 100 80 60 40 20 0 1000 1200 1400 1600 1800 P Pa 9 0KW h 60Hz 11 2KW h 60Hz Low speed Midium speed High speed...

Page 14: ...es fall in the pipe system during the time of installation The connecting pipe should not be installed until the indoor and outdoor units have been fixed already Keep the connecting pipe dry and do no...

Page 15: ...e by condensation Pass the bound connecting pipe through the wall conduit from outside Be careful of the pipe all ocation to do no damage to the tubing Connect the pipes Then open the stem of stop val...

Page 16: ...he air comes in the sound of the pump changes and the indicator of compound meter turns below zero Then fasten the nut When the pumping has finished close the Lo lever of the manifold valve completely...

Page 17: ...rs The wiring of 71T1 to 160T1 indoor unit please refer to Fig 11 1 and Fig 11 2 is the communication wiring for 200T1 250T1 and 280T1 indoor unit The reserved function is indicated in broken line tab...

Page 18: ...1234 SW1 ON 1234 1 means factory test mode 0 means auto addressing mode default setting 1 means DC fan is chosen 0 means AC fan is chosen 00 means DC fanstatic pressure is 0 reserved reserve d J1 J2...

Page 19: ...r unit communication is abnormal Condenser sensor check point is abnormal or outdoor temp sensor is abnomal Water level switch is abnormal Mode conflict Run lamp flashes at 2 5Hz The timer lamp flashe...

Page 20: ...r conditioner is pre heated by turning on the power 19 Low pressure pipe Hi pressure pipe Electric throttle part Liquid branch pipe 9 5 9 5 15 9 15 9 Gas branch pipe 10m 25 4 12 7 Accordingto theuser...

Reviews: