M‐Thermal Split
48
201909
Midea M‐Thermal Split Ser
vice Manual
4.5
E5, E6, E9, EA Troubleshooting
Digital display output
Description
E5 indicates an air side heat exchanger refrigerant outlet temperature sensor error.
E6 indicates an outdoor ambient temperature sensor error.
E9 indicates a suction pipe temperature sensor error.
EA indicates a discharge temperature sensor error.
M‐Thermal Split stops running.
Error code is displayed on outdoor unit main PCB and user interface.
Possible causes
Temperature sensor not connected properly or has malfunctioned.
Damaged outdoor unit main PCB.
Midea CAC Confidential