M‐Thermal Split
201909 21
P
art 3 ‐
Con
tr
ol
When the suction pressure drops below 0.14MPa the system displays P0 protection and the unit stops running. When the
suction pressure rises above 0.3MPa, the compressor enters re‐start control.
5.3
Discharge Temperature Protection Control
This control protects the compressor from abnormally high temperatures and transient spikes in temperature.
Figure 3‐5.3: High discharge temperature protection control
When the discharge temperature rises above 115°C the system displays P4 protection and the unit stops running. When
the discharge temperature drops below 95°C, the compressor enters re‐start control.
Figure 3‐5.4: Low discharge temperature protection control
When the discharge temperature(Tp) is below sunction temperature(Th) for more than 5 minutes after compressor
operates for 15 minutes, the system displays EA protection and the unit stops running. When the discharge temperature
rises to 27°C or higher, the compressor enters re‐start control.
5.4
Compressor Current Protection Control
This control protects the compressor from abnormally high currents.
Figure 3‐5.5: Compressor current protection control
Table 3‐5.1: Current limitation for compressors
Model name
MHA‐V4(6)W/D2N8
MHA‐V8(10)W/D2N8
Compressor model
SVB172FNPMC‐L
SVB220FLGMC‐L
Current
max
18A
19A
When the compressor current rises above Current
max
the system displays P3 protection and the unit stops running. When
the compressor current drops below Current
max
, the compressor enters re‐start control.
Discharge temperature > 115°C
Discharge temperature < 95°C
Normal operation
High discharge temperature protection, error code P4 is displayed
Tp ≤ Th for more than 5 minutes
Tp ≥ Th
Normal operation
Low discharge temperature protection, error code EA is displayed
Current > Current
max
Current < Current
max
Normal operation
Compressor current protection, error code P3 is displayed
Midea CAC Confidential
Summary of Contents for SMK-60/CGN8
Page 1: ...M Thermal Split Series Commercial Air Conditioners R32 Service Manual Midea CAC Confidential...
Page 3: ...M Thermal Split 2 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...
Page 7: ...M Thermal Split 6 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...
Page 15: ...M Thermal Split 14 201909 Midea M Thermal Split Service Manual Midea CAC Confidential...