13
Be sure, using a torque wrench to tighten the service port cap (after using the service port), so that it prevents the gas
leakage from the refrigeration cycle.
Procedure
1. Recheck the piping connections.
2. Open the valve stem of the 2-way valve
counterclockwise approximately 90’, wait 10
seconds, and then set it to closed position.
Be sure to use a hexagonal wrench to operate
the valve stem.
3. Check for gas leakage.
Check the flare connection for gas leakage
4. Purge the air from the system.
Set the 2-way valve to the open position and
remove the cap from the 3-way valve’s service
port.
Using the hexagonal wrench to press the valve
core pin, discharge for three seconds and then wait
for one minute.
5. Use torque wrench to tighten the service port cap
to a torque of 1.8 kgf.m. (18n.m)
6. Set the 3-way valve to the opened position.
7. Mounted the valve stem nuts to the 2-way and
3-way valves.
8. Check for gas leakage.
At this time, especially check for gas leakage from
the 2-way and 3-way stem nuts, and from the
service port.
Caution:
If gas leakage is discovered in step (3) above, take
the following measures.
If the leaks stop when the piping connections are
tightened further, continue working from step (4).
If the gas leaks do not stop when the connections are
retightened, repair the location of the leak, discharge all
of the gas through the service port, and then recharge
with the specified amount of gas from a gas cylinder.
Summary of Contents for MSV1-09HRDN1-QC2
Page 9: ...6 3 Dimension 3 1 Indoor Unit MSV1 09HRDN1 QC2 A 795 165 270 MSV1 12HRDN1 QC2 A 285 845 165...
Page 10: ...7 3 2 Outdoor Unit MOC 09HDN1 QC2 MOC 12HDN1 QC2...
Page 12: ...9 5 Refrigerant cycle diagram...
Page 13: ...10 6 Wiring diagram 6 1 Indoor Unit MSV1 09HRDN1 QC2 A MSV1 12HRDN1 QC2 A...
Page 14: ...11 6 2 Outdoor Unit MOC 09HDN1 QC2 MOC 12HDN1 QC2...
Page 36: ...33 LED1 LED4 LED5 LED6...