12
7. Installation details
7.1 Wrench torque sheet for installation
Outside diameter
Torque
mm
inch
Kg
f.
m
Ф
6.35
1/4
1.8
Ф
9.52
3/8
4.2
Ф
12.7
1/2
5.5
7.2 Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Grade
Unit
9K
12K
mm
2
1.5
1.5
7.3 Pipe length and the elevation
Pipe size
Capacity
Btu/h
G
as
Liquid
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional
refrigerant
(g/m)
9k
3/8’’ (
Ф
9.52)
1/4’’ (
Ф
6.35)
5
8
20
30
12k
1/2’’ (
Ф
12.7)
1/4’’ (
Ф
6.35)
5
8
20
30
Caution:
Capacity is base on standard length and maximum allowance length is base of reliability.
Oil trap should be installed per 5-7 meters.
7.4 Air purging of the piping and indoor unit
Required tools:
Hexagonal wrench; adjustable wrench; torque wrenches, wrench to hold the joints and gas leak detector.
Note:
The air in the indoor unit and in the piping must be purged. If air remains in the refrigeration piping, it will affect the
compressor, reduce the cooling capacity, and could lead to a malfunction of unit.
Summary of Contents for MSV1-09HRDN1-QC2
Page 9: ...6 3 Dimension 3 1 Indoor Unit MSV1 09HRDN1 QC2 A 795 165 270 MSV1 12HRDN1 QC2 A 285 845 165...
Page 10: ...7 3 2 Outdoor Unit MOC 09HDN1 QC2 MOC 12HDN1 QC2...
Page 12: ...9 5 Refrigerant cycle diagram...
Page 13: ...10 6 Wiring diagram 6 1 Indoor Unit MSV1 09HRDN1 QC2 A MSV1 12HRDN1 QC2 A...
Page 14: ...11 6 2 Outdoor Unit MOC 09HDN1 QC2 MOC 12HDN1 QC2...
Page 36: ...33 LED1 LED4 LED5 LED6...