R410a tropical air-cooled scroll chiller unit 60Hz MCAC-ATSM-2014-09
140 Installation
2) Installation mode II
(less than 8 modules)
Water flow switch
Drill dead hole at the
position, and move the
total effluent temperature
sensor at No.0 address to
the position
No.1 unit
No.0 address(main unit)
No.n unit (n
≤8)
No.(n-1) unit
No.(2n-3) address
No.(2n-1) address
No.1 address
No.(2n-4) address
No.(2n-2) address
Pump
n : the module quantity, max8
Notices :
1) For installation of multi-module, the most modules should be not more than 8 modular units.
2) For installation of multi-module, please drill a dead hole(
Φ
9mm) at the total water outlet pipeline,
and move the total water effluent temperature sensor at No.0 address to the hole.
3.4 MGBT-F180W/DN1
Installation of single-module water system pipeline
Total water outlet temperature sensor
Water outlet
Water inlet
Electric control box