Midea MAD50P1ZWS Owner'S Manual & Installation Manual Download Page 8

Safety 

Precautions

 Page 8 

 

Repair and maintenance to electrical components shall include initial safety checks and component 
inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be 
connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately 
but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be 
reported to the owner of the equipment so all parties are advised.  
Initial safety checks shall include:  
That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking; 
That there no live electrical components and wiring are exposed while charging, recovering or purging 
the system; That there is continuity of earth bonding.

 8)Checks to the refrigeration equipment
    Where electrical components are being changed, they shall be fit for the purpose and to the correct 
    specification. At all times the manufacturer's maintenance and service guidelines shall be followed. If in 
    doubt consult the manufacturer's technical department for assistance. The following checks shall be 
    applied to installations using flammable refrigerants: 
    The charge size is in accordance with the room size within which the refrigerant containing parts are 
    installed; 
    The ventilation machinery and outlets are operating adequately and are not obstructed; 
    If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence 
    of refrigerant; Marking to the equipment continues to be visible and legible. Markings and signs that 
    are illegible shall be corrected; 

Refrigeration pipe or components are installed in a position where they are unlikely to be exposed 

1)During repairs to sealed components, all electrical supplies shall be disconnected from the equipment 
being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an 
electrical supply to equipment during servicing, then a permanently operating form of leak detection 
shall be located at the most critical point to warn of a potentially hazardous situation. 
2)Particular attention shall be paid to the following to ensure that by working on electrical components, 
the casing is not altered in such a way that the level of protection is affected. This shall include damage 
to cables, excessive number of connections, terminals not made to original specification, damage to 
seals, incorrect fitting of glands, etc.  Ensure that apparatus is mounted securely. Ensure that seals or 
sealing materials have not degraded such that they no longer serve the purpose of preventing the 
ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer's 
specifications.
NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection 
equipment. Intrinsically safe components do not have to be isolated prior to working on them.

9)Checks to electrical devices

7.Repairs to sealed components 

Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will 
not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe 
components are the only types that can be worked on while live in the presence of a flammable 
atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts 
specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere 
from a leak.

8.Repair to intrinsically safe components 

to any substance which may corrode refrigerant containing components, unless the components are 
constructed of materials which are inherently resistant to  being corroded or are suitably protected 
against being so corroded.

Summary of Contents for MAD50P1ZWS

Page 1: ...DEHUMIDIFIER Owner s Manual Installation Manual IMPORTANT NOTE Read this manual carefully before installing or operating your new machine Make sure to save this manual for future reference...

Page 2: ...tures 13 Removing the collected water 15 Other features 14 Clean the grille and case 17 Clean the bucket 17 Troubleshooting Tips 18 Clean the air filter 17 When not using the unit for long time period...

Page 3: ...the unit Do not use the machine near flammable gas or combustibles such as gasoline benzene thinner etc Do not drink or use the water drained from the unit Do not take the water bucket out during oper...

Page 4: ...n damaged contact a technician or customer service for assistance In a thunderstorm the power must be cut off to avoid damage to the machine due to lightning Do not run cord under carpeting Do not cov...

Page 5: ...of such waste separately for special treatment is necessary It is prohibited to dispose of this appliance in domestic household waste For disposal there are several possibilities When using this dehu...

Page 6: ...manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants The appl...

Page 7: ...able material 4 Checking for presence of refrigerant The area shall be checked with an appropriate refrigerant detector prior to and during work to ensure the technician is aware of potentially flamma...

Page 8: ...supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers etc If it is absolutely necessary to have an electrical supply to equipment during servicing t...

Page 9: ...ions on the pipe work are to take place Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available 10 Detection of flammable refrigerants The fo...

Page 10: ...g order has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release Consult manufacturer if in doubt The recovered r...

Page 11: ...al performance of our products the design specifications of the unit are subject to change without prior notice Control panel Panel Water level window Water bucket Water bucket Handle both sides Handl...

Page 12: ...ure damage The dehumidifier must be operated in an enclosed area to be most effective Close all doors windows and other outside openings to the room A dehumidifier operating in a basement will have li...

Page 13: ...ing the filter press the Filter button and the light will go off Press the filter button for 3 seconds when the unit is on or off to initiate the Wireless connection mode The LED DISPLAY shows AP to i...

Page 14: ...the bucket is full or when the bucket is removed or not replaced in the Wait 3 minutes before resuming operation After the unit has stopped it can not be restart operation in the first 3 minutes This...

Page 15: ...aining until start The selected time will register in 5 seconds and the system will automatically revert back to display the previous humidity setting When the Auto Start Auto Stop times are set withi...

Page 16: ...ale threaded end When you remove the plastic cover if there is some water in the back drain outlet of the unit you must dry it Make sure the hose is secure so there are no leaks and the end of the hos...

Page 17: ...nd add a little mild detergent Swish it around in the bucket empty and rinse Note Do not use a dishwasher to clean the bucket After clean the bucket must be in place and securely seated for the dehumi...

Page 18: ...tion may be loose Intend to use the bucket to collect water but the back drain plug is removed This is normal The dehumidifier has Auto defrost feature These are error codes and protection codes See t...

Page 19: ...n and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the serv...

Page 20: ...1 80g 2 A4 210 290 3 4 5 1 DP DL 2 3 DP DL 4...

Page 21: ...Pg6 Pg10 WARNING for Using R32 R290 Refrigerant...

Reviews: