ODMI-1103-A
VOLT_RST1_ADD=210V, VOLT_LIM1_ADD=200V, VOLT_RST2_ADD=195V, VOLT_LIM2_ADD=185V.
VOLT_LIM_FREQ1_ADD=54Hz, VOLT_LIM_FREQ2_ADD=42Hz.
7.5.4 Compressor current limit protection
If the compressor current exceeds the current limit value for 10 seconds, the compressor frequency will be
limited as below table.
For models except M5OA-36HRDN1-Q.
Cooling mode:
Current frequency(Hz)
Current limit value(A)
Frequency limit
COOL_F10
ICOOLLMT6
Decrease the frequecny to COOL_F4 and
run at COOL_F4 for 3 minutes.
After that,the frequency will be adjusted
according to the capacity demand and rise
to the upper level every 3 minutes
(When
the
frequency>COOL_F4
via
capacity demand).
COOL_F9
ICOOLLMT5
COOL_F8
ICOOLLMT4
COOL_F7
ICOOLLMT3
COOL_F6
ICOOLLMT2
COOL_F5
ICOOLLMT1
If the current frequency is lower than COOL_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>ICOOL,the AC will display the failure for 30 seconds
and stop. The AC will restart 3 minutes later.
Heating mode:
Current frequency(Hz)
Current limit value(A)
Frequency limit
HEAT_F12
IHEATLMT8
Decrease the frequecny to HEAT_F4 and
run at HEAT_F4 for 3 minutes.
After that,the frequency will be adjusted
according to the capacity demand and rise
to the upper level every 3 minutes
(When the frequency>Heat_F4 via capacity
demand).
HEAT_F11
IHEATLMT7
HEAT_F10
IHEATLMT6
HEAT_F9
IHEATLMT5
HEAT_F8
IHEATLMT4
HEAT_F7
IHEATLMT3
HEAT_F6
IHEATLMT2
HEAT_F5
IHEATLMT1
If the current frequency is lower than HEAT_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>IHEAT,the AC will display the failure for 30 seconds
and stop. The AC will restart 3 minutes later.
For M5OA-36HRDN1-Q model:
Cooling mode:
Current
frequency
(
Hz
)
Current limit value
(
A
)
Frequency limit
COOL_F16
ICOOLLMT12
Decrease the frequecny to COOL_F4 and run at
COOL_F4 for 3 minutes.
After that,the frequency will be adjusted according to
the capacity demand and rise to the upper level every
3 minutes
(When the frequency>COOL_F4 via capacity
demand).
COOL_F15
ICOOLLMT11
COOL_F14
ICOOLLMT10
COOL_F13
ICOOLLMT9
COOL_F12
ICOOLLMT8
COOL_F11
ICOOLLMT7
COOL_F10
ICOOLLMT6
Summary of Contents for M2OC-14HRDN1
Page 6: ...ODMI 1103 A 4 Wiring Diagram 4 1 M2OC 14HRDN1 Q 4 2 M2OC 14HRDN1...
Page 7: ...ODMI 1103 A 4 3 M2OC1 18HRDN1 Q M3OC1 21HRDN1 Q 4 4 M2OC 18HRDN1 M3OC 27HRDN1...
Page 8: ...ODMI 1103 A 4 5 M3OC1 27HRDN1 Q M4OC 24HRDN1 Q 4 6 M4OC1 27HRDN1 Q M4OC 27HRDN1...
Page 9: ...ODMI 1103 A 4 7 M4OC 36HRDN1 4 8 M5OA 36HRDN1 Q...
Page 11: ...ODMI 1103 A 5 4 Refrigeration circuit drawing of inverter quintuple type...