64
The power consumption parameter is optional. If some parameter is not be activated in the system, the parameter will
show "--" .
The heat pump capacity is for reference only, not used to judgethe ability of the unit. The accuracy of sensor is ±1
℃
.
The flow rates parameters are calculated according to the pump running parameters,the deviation is different at
different flow rates,the maximum of deviation is 15%.The flow parameters are calculated according to the electrical
parameters of the pump operation.
The operating voltage is different and the deviation is different.
The display value is 0 when the voltage is less than 198V.
NOTE
OPERATION PARAMETER
#01
IDU TARGET FREQUENCY 46Hz
ADDRESS
FREQUENCY LIMITED TYPE 5
FAN SPEED 600R/MIN
SUPPLY VOLTAGE 230V
DC GENERATRIX VOLTAGE 420V
DC GENERATRIX CURRENT 18A
7/9
OPERATION PARAMETER
#01
TW_I PLATE W-INLET TEMP. 30°C
ADDRESS
T2 PLATE F-OUT TEMP. 35°C
TW_O PLATE W-OUTLET TEMP. 35°C
T2B PLATE F-IN TEMP. 35°C
Th COMP. SUCTION TEMP. 5°C
Tp COMP. DISCHARGE TEMP. 75°C
8/9
OPERATION PARAMETER
#01
T4 OUTDOOR AIR TEMP. 5°C
ADDRESS
TF MODULE TEMP. 55°C
T3 OUTDOOR EXCHARGE TEMP. 5°C
P1 COMP. PRESSURE 2300kPa
ODU SOFTWARE 01-09-2018V01
HMI SOFTWARE 01-09-2018V01
9/9