![Midea M-thermal Mono Series Installation And Owner'S Manual Download Page 48](http://html1.mh-extra.com/html/midea/m-thermal-mono-series/m-thermal-mono-series_installation-and-owners-manual_1791188048.webp)
45
10 START-UP AND CONFIGURATION
The unit should be configured by the installer to match the installation environment (outdoor climate, installed options, etc.) and
user expertise.
It is important that all information in this chapter is read sequentially by the installer and that the system is configured as
applicable.
CAUTION
10.1 Climate related curves
The climate related curves can be selected in the user interface. Once the curve is selected, the target water flow temperature
in each mode is calculated by the curve.
It’s possible to select curves even dual room thermostat function is enabled.
The relationship between outdoor temperature (T4/°C) and the target water temperature(T1S/°C) is described in the tables and
pictures. )
Temperature curves for heating mode
T4H1
T4H2
T1SETH2
T1SETH1
T4
T1S (T1S2)
The automatic setting curve is the ninth curve,the ninth curve can be set as following:
State:In the setting the wired controller, if T4H2<T4H1, then exchange their value; if T1SETH1<T1SETH2, then
exchange their value.
T4
≤
- 20
- 19
- 18
- 17
- 16
- 15
- 14
- 13
- 12
- 11
- 10
- 9
- 8
- 7
- 6
- 5
- 4
- 3
- 2
- 1
0
1- T1S
38
38
38
38
38
37
37
37
37
37
37
36
36
36
36
36
36
35
35
35
35
2- T1S
37
37
37
37
37
36
36
36
36
36
36
35 35 35 35 35 35 34 34 34 34
3- T1S
36
36
36
35
35
35
35
35
35
34
34
34 34 34 34 33 33 33 33 33 33
4- T1S
35
35
35
34
34
34
34
34
34
33
33
33 33 33 33 32 32 32 32 32 32
5- T1S
34
34
34
33
33
33
33
33
33
32
32
32 32 32 32 31 31 31 31 31 31
6- T1S
32
32
32
32
31
31
31
31
31
31
31
31 30 30 30 30 30 30 30 30 29
7- T1S
31
31
31
31
30
30
30
30
30
30
30
30 29 29 29 29 29 29 29 29 28
8- T1S
29
29
29
29
28
28
28
28
28
28
28
28 27 27 27 27 27 27 27 27 26
T4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
≥
20
1- T1S
35
35
34
34
34
34
34
34
33
33
33
33
33
33
32
32
32
32
32
32
32
2- T1S
34
34
33
33
33
33
33
33
32
32
32
32 32 32 31 31 31 31 31 31 31
3- T1S
32
32
32
32
32
32
31
31
31
31
31
31 30 30 30 30 30 30 29 29 29
4- T1S
31
31
31
31
31
31
30
30
30
30
30
30 29 29 29 29 29 29 28 28 28
5- T1S
30
30
30
30
30
30
29
29
29
29
29
29 28 28 28 28 28 28 27 27 27
6- T1S
29
29
29
29
29
29
28
28
28
28
28
28 27 27 27 27 27 27 26 26 26
7- T1S
28
28
28
28
28
28
27
27
27
27
27
27 26 26 26 26 26 26 25 25 25
8- T1S
26
26
26
26
26
26
26
25
25
25
25
25 25 25 25 24 24 24 24 24 24
Summary of Contents for M-thermal Mono Series
Page 92: ...NOTE...
Page 93: ......
Page 94: ...16125300002440 V1 0 It Fr Es Pt Pl Tu Ro Ru De Nl Manuals inn various languages...
Page 95: ...A4 105g 100g...
Page 96: ......
Page 97: ......
Page 98: ......