MCAC-CTSM-2014-03 DX type water-cooled screw chiller (PCB Control)
53
⑥
Display if unit gives an alarm, and which unit head gives the alarm exactly;
⑦
Display if the compressor oil heating is finished. If compressor starts, It need to be satisfied that oil
heating time is ‘
0
’or oil temperature is satisfy with compressor start” is ‘
YES
’;
⑧
Display if the starting temperature is satisfied, when compressor starts, it need to be satisfied that
water temperature is satisfied with “compressor start” is‘
YES
’;
⑨
Display if the delay restart is satisfy, when compressor starts, it need to be satisfied that “delay
restart” is‘
NO
’;
⑩
Display if the minimum operation time is satisfy, when compressor stops, it need to be satisfy that
“Min. Running Time Elapsed” is‘
YES
’.
Note:when the compressor has oil temperature sensor, it displays that the oil temperature is satisfied
with compressor start. When it has no oil temperature sensor, it displays the remaining time of oil heating.
It depends on the unit
It displays the refrigerant type on the top left of the screen.
To start the unit must meet the following conditions:
①
“Delaying Restart” need to be “NO”, if it is “YES”, the delay time to start the unit is not reached.
②
“Water Temperature Allow Compressor Start” need to be “YES”, if it is “NO”, that means the current
water temperature is not satisfied with the startup condition of compressor.
③
“Oil Temp. Allow Compressor Start” need to be “YES”, if it is “NO”, that means the current oil
temperature is not satisfy with the startup condition of compressor.
Shutdown must meet the following conditions:
“Min. Running Time Elapsed” need to be“YES”, if it is “NO”, the delay time of shutdown is not
reached.