MCAC-CTSM-2014-03 DX type water-cooled screw chiller (PCB Control)
69
Type
Electric Cable (mm
2
)
Capacity of
Breaker
(A)
Note: It is
recommended that only
copper-conductor
cables are used in this
unit. In high-altitude
areas with high
temperature,
temperature derating
should be considered,
that is, the capacity of
breaker device should
be increased properly.
Phase line
PE line
255
25
16
160
320
35
16
160
400
50
25
250
485
70
35
250
630
95
50
400
860
150
70
400
970
185
95
630
1060
2*70
70
630
1260
2*95
95
630
1490
2*120
120
800
Note: The length of leading-in power cables in the unit cannot exceed 180 m.
3) Cooling and chilled water pump wiring
Chilled water pump wiring for
255
;
320
;
400
;
485; 630; 860 models
contactor
Intermediate relay
control cabinet
wiring terminal
Pump motor