MCAC-CTSM-2014-03 DX type water-cooled screw chiller (PCB Control)
63
Ⅳ
.Electrical control
1.Electrical data
LSBLGXXX/MZ
255
320
400
485
630
860
970
1060
1260
1490
Standard voltage
V
380V 3Ph 50Hz
Voltage range
V
340~420
Max. running current
A
120
148
189
205
277
383
445
458
554
662
Max. power
consumption
kW
80.6
95.5
127.
5
148.
1
188.
2
255.
5
296.
2
329.
6
376.
4
443.
7
Rated current
A
92
119
146
171
213
295
341
365
427
509
Compressor A
Locked rotor Amps.
A
690
780
875
1220
1510
2355
1220
1220
1510
1510
Max. allowed current
A
145.
2
171.
9
229.
6
266.
7
338.
9
460
266.
7
305.
1
338.
9
338.
9
Rated current
A
92
119
146
171
213
295
171
194
213
213
Rated power
kW
53.6
67
85
100
125
173
100
114
125
125
Compressor B
Locked rotor Amps.
A
--
--
--
--
--
--
1220
1330
1510
2355
Max. allowed current
A
--
--
--
--
--
--
266.
7
266.
7
338.
9
460
Rated current
A
--
--
--
--
--
--
171
171
213
295
Rated power
kW
--
--
--
--
--
--
100
100
125
173
Crankcase heater
Voltage
V
380
380
380
380
380
380
380
380
380
380
Total input
kW
0.3
0.3
0.3
0.3
0.3
0.3
0.6
0.6
0.6
0.6
Total Amps.
A
1.36
1.36
1.36
1.36
1.36
1.36
2.72
2.72
2.72
2.72
NOTE:
1). Customer to specify the exact nominal power supply available at site so that electrical components are
selected accurately.
2).Main power must be supplied from a single field supplied and mounted fused circuit breaker.
3).The compressor crankcase heaters must be energized for hours before the unit is initially started or after a
prolonged power disconnection.
4).All field wining must be in accordance with local standards.
5).Neutral line required on 380V-3Ph-50Hz(5 wires) power supply.
6).Rated load Amps values are on nominal conditions.
7).The ±10% voltage variation from the nominal is allowed for a short time not permanent.
2. Electrical components introduction
1) Power protector
This module is used to detect power supply and provide protection in case of phase loss, phase
sequence, and under voltage of incoming line power, so as to prevent damage to the compressor or
other components caused by power failure. Some models also provide protection for overvoltage and
three phase imbalance.