DX type water-cooled screw chiller (PCB Control)
MCAC-CTSM-2014-03
10
3. Specifications
Single head
LSBLGXXX/MZ
255
320
400
485
630
860
Cooling capacity
kW
253
318
400
485
628
859
Power input
kW
53.6
67
85
100
125
173
EER
kW/kW
4.73
4.75
4.71
4.85
5.02
4.97
Semi-hermetic screw compressor
Circuit A
Quantity
1
1
1
1
1
1
Circuit B
Quantity
--
--
--
--
--
--
Capacity Control
%
25%,50%,75%,100% four steps control
(25%,50%-100% Stepless as Option)
Oil recharge
Type
HBR-B01
Circuit A
L
14
14
15
18
23
28
Circuit B
L
--
--
--
--
--
--
Refrigerant
Type
R22
Circuit A
kg
35
40
60
80
110
160
Circuit B
kg
--
--
--
--
--
--
Control Type
TXV
TXV
TXV
TXV
TXV
EXV
Evaporator
Type
Shell-tube Direct Expansion Evaporator
Water content
L
100
150
80
120
340
290
Water flow
m³/h
43.5
54.7
68.8
83.4
108
147.7
Pressure drop
kPa
41
36
73
54
65
65
Connection Type
Victaulic coupling
Max. pressure
MPa
1
1
1
1
1
1
Water inlet/outlet pipe dia.
mm
80
80
100
125
125
150
Condenser
Type
Tube-and shell condenser
Water content
L
150
150
130
160
320
260
Water flow
m³/h
54.4
68.4
86
104.3
135
184.7
Pressure drop
kPa
36
41
22
49
81
41
Max. pressure
MPa
1
1
1
1
1
1
Water inlet/outlet pipe dia.
mm
80
80
100
125
125
150
Unit length
mm
2800
2800
2860
3200
3430
3430
Unit width
mm
1165
1165
1285
1300
1480
1610
Unit height
mm
1350
1350
1420
1450
1600
1730
Shipping weight
kg
1540
1870
2250
2610
2975
3780
Running weight
kg
1840
2070
2550
2910
3375
4180
Safety protection device
The following safety devices are equipped as standard.
High pressure (pressure switch);Low pressure (pressure sensor)
Compressor thermal protection
High discharge temperature on the compressor
Phase monitor; Low-pressure ratio; Low oil level protection
Interrupter protection ;Overload compressor protection
Over-voltage & low- voltage protection
Sensor malfunction protection
Contactor malfunction protection
Freeze protection
Note:
Nominal cooling capacities are based on the following conditions:
Chilled water inlet/outlet temp: 12
℃
/7
℃
; (53.6F/44.6F); Cooling water inlet/outlet temperature 30/35
℃
(86F/96F).
The design fouling factor for both evaporator and condenser are 0.086 m
2
.
℃
/kW, otherwise can be customized.