After the confirmation of the above conditions, prepare the wiring as follows:

1) Never fail to have an individual power circuit specifically for the air conditioner. As for

the method of wiring, be guided by the circuit diagram posted on the inside of control
cover.

2) The screw which fasten the wiring in the casing of electrical fittings are liable to come

loose from vibrations to which the unit is subjected during the course of
transportation. Check them and make sure that they are all tightly fastened. (If they
are loose, it could cause burn-out of the wires.)

3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated

voltage marked on the name plate.

6) Confirm that the cable thickness is as specified in the power source specification.

7) Always install an earth leakage circuit breaker in a wet or moist area.

8) The following would be caused by voltage drop.

Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the

normal function of the overload.

9) The means for disconnection from a power supply shall be incorporated in the fixed

wiring and have an air gap contact separation of at least 3mm in each active(phase)
conductors.

CAUTION

CAUTION

CAUTION

CAUTION

Air and moisture in the refrigerant system have undesirable effects as indicated below:

 Pressure in the system rises.

 Operating current rises.

 Cooling or heating efficiency drops.

 Moisture in the refrigerant circuit may freeze and block capillary tubing.

 Water may lead to corrosion of parts in the refrigeration system.

Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested 
and evacuated to remove any noncondensables and moisture from the system.

Air purging with vacuum pump

Preparation
Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units 
have been properly connected and all wiring for the test run has been completed. Remove 
the service valve caps from both the gas and the liquid side on the outdoor unit. Note that 
both the liquid and the gas side service valves on the outdoor unit are kept closed at this 
stage.

Pipe length and refrigerant amount:

 AIR PURGING

Air purging

12

Connective
pipe length

Less than 5m

More than 5m

Air purging
method

Use vacuum
pump. 

Use vacuum
pump. 

Additional amount of refrigerant to be charged
                           

R22: (Pipe length-5)x30g/m
R410A: (Pipe length-5)x20g/m        

Liquid side:    6.35

R22: (Pipe length-5)x60g/m
R410A: (Pipe length-5)x40g/m        

Liquid side:    9.53

Summary of Contents for INVERTER SPLIT TYPE ROOM AIR CONDITIONER

Page 1: ...ompletely before installing the product If the power cord is damaged replacement work shall be performed by authorised personnel only Installation work must be performed in accordance with the nationa...

Page 2: ...use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the...

Page 3: ...ring standard regulation and this installation instructions An independent circuit and single outlet must be used If electrical circuit capacity is not enough or defect found in electrical work it wil...

Page 4: ...ated by arrows from wall or other obstacles Do not place animals and plants in the path of the air inlet or outlet Take the air conditioner weight into account and select a place where noise vibration...

Page 5: ...e 60c m abo ve 30cm above Air Filter Air Outlet 30cm above Wrapping tape B 200cm above Additional drain pipe Accessories Parts you must purchase Consult the dealer about the pipe size 6 35 9 53 12 7 9...

Page 6: ...mensions are in mm unless otherwise stated 1 Determine hole positions according to the diagramdetailed in Fig 5 Drill one 1 hole 65mm slanting slightly to outdoor side 2 Always use wall hole conduit w...

Page 7: ...the indoor unit with a cushioning material between the indoor unit and the wall Get it out after finish piping 4 Push the lower part of the indoor unit up on the wall then move the indoor unit from s...

Page 8: ...se sloped downward to drain out the condensed water smoothly CAUTION Install the outdoor unit on a rigid base to prevent increasing noise level and vibration Determine the air outlet direction where t...

Page 9: ...r tube pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing Pipe Reamer Point down Fig 16 Fig 17 Outdoor unit dimension mm WxHxD A mm B mm 530 290 484 600...

Page 10: ...air conditioner and explain to the client until the problem is solved 2 Power voltage should be in the range of 90 110 of rated voltage 3 The creepage protector and main power switch with a 1 5 times...

Page 11: ...oosening the screw as shown in Fig 22 4 Ensure the colour of wires of outdoor unit and the terminal Nos are the same to the indoor s respectively 5 Wrap those cables not connected with terminals with...

Page 12: ...connecting means must be provided and shall be located within sight from and readily accessible from the air conditioner Connecting cable with conduit shall go through the hole of the conduit panel No...

Page 13: ...the fixed wiring and have an air gap contact separation of at least 3mm in each active phase conductors CAUTION CAUTION CAUTION CAUTION Air and moisture in the refrigerant system have undesirable eff...

Page 14: ...ully open the handle Lo of the manifold valve 4 Operate the vacuum pump to evacuate After starting evacuation slightly loose theflare nut of the Lo valve on the gas pipe side and check that the air is...

Page 15: ...If bubbles come out the pipes have leakage 2 Leak detector Use the leak detector to check for leakage Test running Safety and leakage check 14 TEST RUNNING Manual control button AUTO COOL Perform tes...

Page 16: ...CS120I BP9A1 LH 202000192327 20110613 The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details...

Reviews: