Defrost (only applicable to the heating mode)
1.
the intelligent defrost
In the heating mode, the electric control board checks and compares the temperature of indoor room and indoor
coil pipe after the compressor works for a while; judge whether the outdoor heat exchanger part is frosted or not
according to conditions such as the change of indoor coil pipe temperature; if it is judged as frosted, it automatically
enters defrosting process. When defrosting, close the indoor and outdoor blower fan and four-way valve.
2. Outdoor PCB for defrost.
In the heating mode, the unit defrost by outdoor control board
:
unit start defrost shall
①
all meet the following conditions
:
a
、
compressor continuous running over 7 minutes
;
b
、
defrost relay shut off
;(
-5
℃
)
c
、
compressor cumulate running time over 50 minutes.
;
first defrost interval time is 50 minutes, later defrost interval time decided by last defrost time.
②
Defrost
time(minute)
Next defrost interval
time(minute)
15 30
10--15 40
7--10 60
3--7 70
≤
3 80
(
2
)
end defrost condition(meet one of follows)
a
、
defrost time have fifteen minutes.
b
、
defrost relay turn on
;(>
8
℃
)
c
、
press ON/OFF key in defrost process.
3. Outdoor sensor for defrost
unit start defrost shall meet one of the following conditions
:
compressor cumulate running time over 30 minutes and it continuous running over 3 minutes, the temperature of
coil pipe of the outdoor units is equal to or less than
-
15
for one minutes (Tp2
≤
℃
-15
).
℃
compressor cumulate running time over 40 minutes and it continuous running over 3 minutes, the temperature of
coil pipe of the outdoor units is equal to or less than
-
5
for one minutes (Tp2
≤
℃
-15
).
℃
Air conditioner first power on or it wait over 30 minutes ,the temperature of coil pipe of the outdoor units is
equal to or less than
-
2
(Tp2
≤
℃
-15
)
℃
end defrost condition
②
(meet one of follows)
The temperature of coil pipe of the outdoor units is more than 15
(Tp2
≥
℃
-15
).
℃
Defrost time has fifteen minutes.
Summary of Contents for CSU 12HCAA
Page 48: ...2005 12 20...
Page 49: ......
Page 57: ...9 59...
Page 59: ...11 59...
Page 60: ...12 59...
Page 61: ...13 59...
Page 62: ...14 59...
Page 63: ...15 59...
Page 64: ...16 59...
Page 65: ...17 59...
Page 66: ...18 59...
Page 67: ...19 59 Installation Guide 4 Indoor unit and outdoor unit explosion diagram and spare parts list...
Page 68: ...20 59 CS 23H3 V77AY1A CS 25H3 V AY1A CS 32H3 V AH4 INDOOR UNIT...
Page 69: ...21 59 CS 51H3 H AH1 INDOOR UNIT...
Page 70: ...22 59 CS 66H3 N AS INDOOR UNIT...
Page 71: ...23 59 CS 88H3 Q AT INDOOR UNIT...
Page 72: ...24 59 KFR 23GW AC CS 25H3 V AY1A OUTDOOR UNIT...
Page 73: ...25 59 CS 32H3 V AH4 OUTDOOR UNIT...
Page 74: ...26 59 CS 51H3 H AH1 OUTDOOR UNIT...
Page 75: ...27 59 CS 66H3 N AS OUTDOOR UNIT...