28
Installation & Maintenance Manual
5-2 Disassembly of indoor unit
Release the bottom edge of indoor unit from the mounting plate.
Use Allen wrench
In case the method in left column cannot be taken
As shown in Figure below, use Allen wrench to pull
downward the bottom edge of indoor unit, and then pull
out the unit slight so as to release the bottom buckles;.
If the method cannot be taken, just remove the face plate.
As shown in Figure below, insert the allen wrench into
the left and right square openings; and then push the
allen wrench upward so as to descend the indoor unit,
Insert the Allen
wrench, and hook the end.
Allen wrench (4cm)
Square opening
Push
Downward
5-3 Refrigerant replenishment
Detailed operation steps are listed as follow:
Align and connect the gas bomb onto access door of gas valve;
Carry out the air purge for pipeline (or hose) from gas bomb of refrigerant;
Replenish refrigerant of specified volume for normal operation of the air conditioner.
Connecting pipe
Indoor unit
Shutoff valve
Outdoor unit
Liquid pipe
Gas pipe
Charging hose
Access door
(R-22 liquid ) charging
Spring balance
Charging bottle
of coolant
Operation valve of
gas bomb for coolant
Note:
Pipe length (m)
Refrigerant replenishing
volume for unit(g)
If connecting pipe length is over 7m, refrigerant replenishment is required.
Refrigerant replenishing volume for cooling/heating unit are listed as follow: A = 15g/m * (L-7) .
(A in the formula indicates the refrigerant replenishing volume in g; L indicates connecting pipe length in m)
Note: maximum length of connecting pipe for models 25 Series must not be longer than 10m, and the maximum
length of connecting pipe for models 35/50/70 Series must not be longer than 15m.
1. During charing operation, do not turn over the gas
bomb for refrigerant replenishing for fear of any
problem;
2. To keep the high pressure in the gas bomb, please
heat it by warm water (40
) in cold seasons. Do not
put it on fire, or heat it by hot steam.
VI. Installation instructions
Summary of Contents for CSU 12HCAA
Page 48: ...2005 12 20...
Page 49: ......
Page 57: ...9 59...
Page 59: ...11 59...
Page 60: ...12 59...
Page 61: ...13 59...
Page 62: ...14 59...
Page 63: ...15 59...
Page 64: ...16 59...
Page 65: ...17 59...
Page 66: ...18 59...
Page 67: ...19 59 Installation Guide 4 Indoor unit and outdoor unit explosion diagram and spare parts list...
Page 68: ...20 59 CS 23H3 V77AY1A CS 25H3 V AY1A CS 32H3 V AH4 INDOOR UNIT...
Page 69: ...21 59 CS 51H3 H AH1 INDOOR UNIT...
Page 70: ...22 59 CS 66H3 N AS INDOOR UNIT...
Page 71: ...23 59 CS 88H3 Q AT INDOOR UNIT...
Page 72: ...24 59 KFR 23GW AC CS 25H3 V AY1A OUTDOOR UNIT...
Page 73: ...25 59 CS 32H3 V AH4 OUTDOOR UNIT...
Page 74: ...26 59 CS 51H3 H AH1 OUTDOOR UNIT...
Page 75: ...27 59 CS 66H3 N AS OUTDOOR UNIT...