MCAC-RTSM-2012-01 M-thermal Technical Manual
9
5. Specifications
5.1 Specifications of outdoor units
DC Inverter outdoor unit
LRSJF-V120/SN1-610
LRSJF-V140/SN1-610
Power supply
Ph-V-Hz
3-380
~
415-50
3-380
~
415-50
Max. current
A
9
9
Heating
Capacity
kW
12
14
COP
kW/kW
4.17
4.13
Ambient Temp.
℃
-20
~
43
-20
~
43
Cooling
Capacity
kW
8.8
8.8
COP
kW/kW
2.22
2.28
Ambient Temp.
℃
15
~
43
15
~
43
Unit
Dimension (W×H×D)
mm
900×1327×320
900×1327×320
Packing (W×H×D)
mm
1016×1456×435
1016×1456×435
Net/gross weight
kg
89/101
89/101
Noise level
dB(A)
58
58
Refrigerant
type/quantity
kg
R410a/2.7kg
R410a/2.7kg
system pressure
MPa
4.4/2.6
4.4/2.6
Refrigerant
pipe
Liquid side
mm
Ф9.52
Ф9.52
Gas side
mm
Ф16
Ф16
Max. length
m
50
50
Max. difference between
outdoor unit and indoor unit
m
15
15
Compressor
Model
TNB306FPNMC
TNB306FPNMC
Type
Rotary
Rotary
Brand
Mitsubishi
Mitsubishi
Capacity
kW
9.88
9.88
Input
w
3010
3010
Locked rotor current
A
45
45
Rate current
A
9.3
9.3
Crankcase
W
30
30
Fan motor
Brand
Panasonic
Panasonic
Model
WZDK100-38G
(
×2
)
WZDK100-38G
(
×2
)
Type
DC MOTOR
DC MOTOR
Input
w
100*2
100*2
Output
w
110*2
110*2
Speed
r/min
800
800
Outdoor coil
Number of rows
2
2
Tube pitch(a)x row pitch(b)
mm
25.4/22
25.4/22
Tube dia. and type
mm
7.94(female screw)
7.94(female screw)
Fin space
mm
1.7
1.6
Fin type (code)
Hydrophilic aluminum
Hydrophilic aluminum
Coil length x height
1276*870
1276*870
Number of circuits
7
7
Loading
Quantity
20'/40'/40H
Pcs
28/58/58
28/58/58
Summary of Contents for CSD80GN1
Page 27: ...1 4 Dimensions of the outdoor unit 1 5 Installation space 1 Single unit installation...
Page 28: ...2 Parallel connect the two units or above 3 Parallel connect the front with rear sides...
Page 50: ......
Page 59: ......
Page 60: ......
Page 70: ...M thermal technical manual part 3 3 4 Field setting table...