MCAC-RTSM-2012-01 M-thermal Technical Manual
12
6. Performance data
6.1 Heating performance data of 14kw model
LWE[
℃
]
25
32
40
43
50
Tamb [
℃
]
HC[W]
PI[W]
COP
HC[W]
PI[W]
COP
HC[W]
PI[W]
COP
HC[W]
PI[W]
COP
HC[W]
PI[W]
COP
-20
4850
1725
2.81
3511
1887
1.53
/
/
/
/
/
/
/
/
/
-10
6943.5
2471
2.81
6426
2758
2.33
5476
3094
1.77
5120
3220
1.59
/
/
/
-5
10555
3586
2.94
8935
3327
2.69
7804
3722
2.1
7391
3883
1.9
/
/
/
0
9138
3662
2.5
11254
4115
2.73
10101
4353
2.32
9317
4274
2.18
/
/
/
2/1
12614
3835
3.29
13017
4244
3.07
10882
4410
2.47
9922
4369
2.27
/
/
/
7/6
15601
3851
4.05
14871
4251
3.5
13036
4472
2.92
11897
4410
2.7
6531
3293
1.98
15/12
17258
3629
4.76
17077
4046
4.22
14503
4003
3.62
13969
4205
3.32
7162
2676
2.68
25/17
13570
2331
5.82
14152
2640
5.36
11336
2573
4.41
7696
2288
3.36
6299
2029
3.1
35/24
/
/
/
/
/
/
13060
2769
4.72
10902
2530
4.31
6059
1781
3.4
6.2 Cooling performance data of 14kw model
Remark:
CC= cooling capacity PI = power input HC = heating capacity
LWE[
℃
]
10
15
20
Tamb [
℃
]
CC[W]
PI[W]
EER
CC[W]
PI[W]
EER
CC[W]
PI[W]
EER
15
4120
1289
3.2
/
/
/
/
/
/
20
5122
1378
3.72
11441
2980
3.84
/
/
/
25
5584
1450
3.85
12009
3217
3.73
14153
3587
3.95
30
5468
1608
3.41
11349
3504
3.24
13596
3504
3.88
35
5463
2110
2.59
10264
3836
2.68
12326
4272
2.89
43
5922
3259
1.82
7357
3365
2.19
8853
3450
2.57
Summary of Contents for CSD80GN1
Page 27: ...1 4 Dimensions of the outdoor unit 1 5 Installation space 1 Single unit installation...
Page 28: ...2 Parallel connect the two units or above 3 Parallel connect the front with rear sides...
Page 50: ......
Page 59: ......
Page 60: ......
Page 70: ...M thermal technical manual part 3 3 4 Field setting table...