GD  Midea  Refrigerant  Equipment  Co.  Ltd                                                                              Service  manual  for  F  Dehumidifier 

2 Electronic function 

2.1 When the unit is just powered on 

When the unit is just powered on or the dropped 

power is just restored, the unit will immediately 

perform the self-diagnosis. The check items include 

the water-full, temperature sensor and humidity 

sensor. If there is no defect, the power indicator will 

flash at 0.5Hz while all other indicators are off. All 

buttons are invalid except the ON/OFF button. 

2.2 Operating under setting humidity 

        When the ON/OFF button is pressed for the first 

time after the unit is powered on or the power is just 

restored from dropping, the unit will operate with a 

original factory humidity 60%RH and the power 

indicator will light. Under this condition, the humidity 

can be set by pressing the Humidity Up/Down 

buttons. When the indoor humidity is 5% higher than 

the setting humidity, the compressor will be on. 

When the indoor humidity is lower than the setting 

humidity, the compressor will be off and the fan will 

stop operating 3 minutes after the compressor is 

shut down. If the indoor humidity is getting 5% 

higher than the setting humidity, the fan will be on 

immediately and the compressor will start too. 

2.3 Continuous Dehumidifying mode 

        The compressor and the fan motor will always 

be on and the Continue and power indicator will be 

on. The LED will display the indoor humidity. Setting 

humidity is not available. 

2.4 Stop operation 

        When the unit is stopped operation by pressing 

the ON/OFF button, the compressor and the fan will 

shut down and all indicators will be off. The time for 

defrost will be cleared. When the unit is restarted by 

pressing the ON/OFF button, the unit will start with 

previous set mode. Whether the defrost function 

starts need to be prejudged. The self-diagnosis 

function will just check the water-full defect. The fan 

motor will work same as the compressor. 

2.5 Compressor delay start 

When the mode is changed but the compressor 

does not start or the unit restart after stop working, if 

the compressor accord with it’s starting condition, 

the fan motor will start immediately while the 

compressor will delay 3 seconds to re-start. 

2.7 Protection and failure mode 

2.7.1 Water full protection. When the water tank is 

full , the compressor and fan motor will shut down 

and the water full indicator will flash with LED 

displaying P2. Under this situation, all button is out 

of service. After the water is poured, the unit will 

restore operating as previous setting. 

2.7.2 Anti icing protection. 

2.7.2.1 If the time accumulates up to 15 minutes 

with compressor operating and the temperature of 

evaporator lower than -1

o

C, the Anti-icing protection 

function will be activated. 

2.7.2.2 When the protection is activated, the 

compressor will be off while the fan motor is on with 

high speed, and the Turbo indicator will be on with 

the LED displaying P1. The time will also be 

cleared. 

2.7.2.3 If the situation that compressor is off and fan 

is on has lasted for 6 minutes or the ON/OFF button 

is pressed, the unit will stop anti-icing protection 

function. 

2.7.2.4 After the Anti-icing function is completed, the 

unit will restore operation as previous mode or stop 

if the Anti-icing function is completed by pressed the 

ON/OFF button. 

2.7.3 Sensor failure check. When the output voltage 

of sensor is lower than 0.5V or higher than 4.95V, 

the unit will alarm and the LED displays E1 for 

humidity sensor failure and E2 for temperature 

sensor failure. Under this situation, the compressor 

and the fan motor will shut down and the Power 

indicator will flash at 5Hz. All buttons is out of 

service. After the defect is cleared, the unit will not 

work until the power to the unit is re-stored. 

2.7.4 When the water full and sensor failure occur 

together, the water full alarm has the priority on 

display. 

2.7.5 compressor protection: under all modes, the 

compressor will delay 3 minutes to start after it stop.   

   

 

Summary of Contents for CE-CF0.3BD/N3-F

Page 1: ...0 Website www mideaaircon com Service manual CAUTION BEFORE SERVICING THE UNIT READ THE SAFETY PRECAUTIONS IN THIS MANUAL ONLY FOR AUTHORIZED SERVICE PERSONNEL MODELS CE CF0 3BD N3 F CE CFZ0 3BD N3 F ...

Page 2: ...ecautions prior to servicing the unit 1 1 SAFETY PRECAUTIONS 1 When servicing the unit set the POWER SWITCH to OFF and unplug the power cord 2 Inspect the service cord for damage or wear If a short circuit is found replace all parts which have been overheated or damaged by the short circuit 3 After servicing the unit make an insulation resistance test to protect the customer from being exposed to ...

Page 3: ...nit is turned on and dark after the unit is turned off 3 FULL WATER indicator Lights up when the bucket is full and the unit stops operating 4 CONTINUE indicator Lights up when the unit is on CONTINUOUS DEHUMIDIFYING mode 5 HUMIDITY UP Button When the unit is operating the setting humidity will go up by pressing this button every time the range of justment is from 35 RH to 80 RH 6 HUMIDITY DOWN Bu...

Page 4: ...an motor will work same as the compressor 2 5 Compressor delay start When the mode is changed but the compressor does not start or the unit restart after stop working if the compressor accord with it s starting condition the fan motor will start immediately while the compressor will delay 3 seconds to re start 2 7 Protection and failure mode 2 7 1 Water full protection When the water tank is full ...

Page 5: ... temperature sensor is defective the motors of the compressor and the fan will be shut down and the power indicator will flash at 5 Hz Power indicator flashes at 5 Hz The connector CN3 in main PCB is loosed Place it properly Pipe temperature sensor trouble Replace pipe temperature sensor Trouble in input circuit of water level switch of drive board components Water level switch broken Replace swit...

Page 6: ...5 3 1 3 Humidity sensor check 3 1 4 Fail to start or fail to start motor 3 1 5 Abnormal noise Humidity display is chaos Water on the Humidity sensor board Dry it over heat Humidity sensor board trouble or main PCB defective Replace humidity sensor board trouble or main PCB ...

Page 7: ...ct w ire Refer to wiring diagram for terminal identification Loose Repair or replace loss e terminal Main PCB failure Select fan speed and Check the voltage of P1 P2 on main PCB Replace the main PCB if no voltage Capacitor Discharge capacitor before testing Test capacitor Replace if not within 10 of manufacture s rating replace if shorted open or damaged Fan motor w ill not run Will not rotate Fan...

Page 8: ...nd replace if not within 10 of manufactures rating Room structure Take proper measures to make the door and window s sealed w ell if gap is found Air flow Clean or remove if any barrier is found to block the inlet outlet wind flow of the unit Less refrigerant Check the tubes for reasons of leakage Recycle the refrigerant correct the leakage points and recharge Capillary tube Regulate the flow if c...

Page 9: ...ce manual for F Dehumidifier 8 Humidity sensor Replace it frequently Main PCB Check and replace the main PCB 4 WIRING DIAGRAM 4 1 For models 5 EXPLODED VIEWS See attached files 6 SPECIFICATIONS See attached files CE CF0 3BD N3 F CE CFZ0 3BD N3 F ...