PD-HW15-SP COVER REMOVAL AND WIRING

INSTALLATION (CONTINUED)

PD-415R-SP / PD-420R-SP MOUNTED
TO VISIONFRAME™ MONITOR WALL

Rack Mount Screws (4)

Threaded 

Clips (2)

Rack Mount Screws (2)

Rack Mount Screws (2)

1) Remove two (2) cover screws to access wiring. 

(FIGURE A) 

2) Wire the device though electrical fitting openings as shown. 

(FIGURE A)

  The input (line) of the PD-HW15-SP must be

  hardwired directly to an electrical 

  distribution panel.

• 

The output (load) of the PD-HW15-SP must be

  hardwired directly to an electrical junction

  box or other AHJ-approved connection.

•  Cord and plug type connections to the 

  PD-HW15-SP are explicitly prohibited.

• 

Ground conductor must be green with

  or without yellow stripe(s) and must be

  connected to earth ground at the

  service equipment or other

  acceptable building earth ground.

3) Replace cover prior to restoring power.

Must be installed by Qualified Electrical Personnel (Licensed Electrical Contractor)

 

FIGURE A

GROUND WIRES

BLACK

WHITE

BLACK

WHITE

INPUT

(LINE)

OUTPUT

(LOAD)

Cover Screws (2)

Bracket 

Mounting

Screws

Page 9

PD-HW15-SP MOUNTED 

IN A STANDARD 19” RACK

Rack Mount Screws (2)

10-32 Sliding Nuts (2)

CAUTION:

 To be installed with a minimum of 14 AWG (2.5 mm

2

) wire that complies 

with local electrical codes.

!

CAUTION:

 Conductors used to connect device should

be as short as possible.

!

Summary of Contents for PD-415R-SP

Page 1: ...utomatically powers outlets off during over under voltage conditions and automatically restores power when voltage returns to normal Thermal circuit breaker overload protection Advanced EMI RFI filter...

Page 2: ......

Page 3: ...ground pin of the AC plug Assurez vous cet appareil est connect une source d alimentation C A avec mise la terre Assurez vous cet appareil est branch sur une source d alimentation fournissant les n ce...

Page 4: ...occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged...

Page 5: ...ges 8 9 Specifications Page 10 Warranty Page 11 Available in 15A or 20A models and in rackmount half rack or hard wired form factors 15A only Series Protection products provide instantaneous protectio...

Page 6: ...SP 1 2 4 7 5 6 3 ON PD 415R SP 7 4 6 5 2 3 15 AMP POWER CENTER PROTECTED WHEN LIT UNDERVOLTAGE WHEN LIT OVERVOLTAGE WHEN LIT POWER ON OFF 120V TOTAL 15A 60Hz PD 415R SP SWITCHED 20 AMP POWER CENTER P...

Page 7: ...ER TO MODELS FOR AMPERAGE RATING POWER LED Illuminates green to indicate operational status OVERVOLTAGE UNDERVOLTAGE LEDS Overvoltage LED indicates red when overvoltage condition is present Undervolta...

Page 8: ...FTER RACK EAR REMOVAL Rack Mount Screws 4 1 2 10 32 Sliding Nut 2 Rack Mount Screws 4 PD 415R SP PD 420R SP BRACKET MOUNTING Rack Mount Screws 4 Rack Mount Screws 4 Rack Mount Screws 2 Page 8 NOTE Any...

Page 9: ...ord and plug type connections to the PD HW15 SP are explicitly prohibited Ground conductor must be green with or without yellow stripe s and must be connected to earth ground at the service equipment...

Page 10: ...s only Lower Limit Cutoff Lower Limit Restore DETAILS SPECIFICATIONS 15 Amp RMS load 120 VAC 20 Amp RMS load 120 VAC 90 150V 5 watts 35 C 330V 186V for a nominal line voltage of 132V 1000 surges 6000...

Page 11: ...NTY IS IN LIEU OF ALL OTHER WARRANTIES OF ANY KIND EITHER EXPRESSED OR IMPLIED INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO THE MAXIMUM EX...

Page 12: ......

Reviews: