background image

MODEL 

NUMBER

PD-915R-SP
PD-920R-SP
PD-415R-SP
PD-420R-SP
PD-HW15-SP

RACKMOUNT
RACKMOUNT
HALF RACK
HALF-RACK
STAND ALONE

CHASSIS

OUTLETS

9
9
4
4
INT. J-BOX

RATING

15A
20A
15A
20A
15A

INPUT

9ft CORD
9ft CORD
9ft CORD
9ft CORD
INT. J-BOX

MODELS

OVER/UNDER

VAC

PROTECTION

SURGE

MODE

SUPPLEMENTAL

OVERCURRENT

PROTECTION

YES
YES
YES
YES
YES

DIFFERENTIAL (L-N)
DIFFERENTIAL (L-N)
DIFFERENTIAL (L-N)
DIFFERENTIAL (L-N)
DIFFERENTIAL (L-N)

YES
YES
YES
YES
NO

SPD

TYPE

3
3
3
3
2

1

2

3

5

6

7

4

FRONT CONVENIENCE POWER OUTLET 

(REFER TO 

MODELS

 FOR AMPERAGE RATING)

POWER LED: 

Illuminates green to indicate operational status.

OVERVOLTAGE / UNDERVOLTAGE LEDS 

Overvoltage LED indicates red when overvoltage

condition is present. Undervoltage LED indicates red when undervoltage condition is present. 

9FT POWER CORD 

(EXCEPT PD-HW15-SP)

POWER SWITCH 

(INTEGRATED CIRCUIT BREAKER INCLUDED ON PD-915R-SP and 

PD-415R-SP ONLY)

REAR POWER OUTLET 

(REFER TO 

MODELS

 FOR AMPERAGE RATING)

SUPPLEMENTAL GROUNDING AND BONDING STUD

RESETABLE 20 AMP CIRCUIT BREAKER 

(PD-420R-SP and PD-920R-SP ONLY)

ELECTRICAL FITTING OPENING INPUT 

(PD-HW15-SP ONLY)

ELECTRICAL FITTING OPENING OUTPUT 

(PD-HW15-SP ONLY)

DESCRIPTION

8

9

10

Page 7

CONNECTIONS, CONTROLS AND INDICATORS (CONTINUED)

Summary of Contents for PD-415R-SP

Page 1: ...utomatically powers outlets off during over under voltage conditions and automatically restores power when voltage returns to normal Thermal circuit breaker overload protection Advanced EMI RFI filter...

Page 2: ......

Page 3: ...ground pin of the AC plug Assurez vous cet appareil est connect une source d alimentation C A avec mise la terre Assurez vous cet appareil est branch sur une source d alimentation fournissant les n ce...

Page 4: ...occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged...

Page 5: ...ges 8 9 Specifications Page 10 Warranty Page 11 Available in 15A or 20A models and in rackmount half rack or hard wired form factors 15A only Series Protection products provide instantaneous protectio...

Page 6: ...SP 1 2 4 7 5 6 3 ON PD 415R SP 7 4 6 5 2 3 15 AMP POWER CENTER PROTECTED WHEN LIT UNDERVOLTAGE WHEN LIT OVERVOLTAGE WHEN LIT POWER ON OFF 120V TOTAL 15A 60Hz PD 415R SP SWITCHED 20 AMP POWER CENTER P...

Page 7: ...ER TO MODELS FOR AMPERAGE RATING POWER LED Illuminates green to indicate operational status OVERVOLTAGE UNDERVOLTAGE LEDS Overvoltage LED indicates red when overvoltage condition is present Undervolta...

Page 8: ...FTER RACK EAR REMOVAL Rack Mount Screws 4 1 2 10 32 Sliding Nut 2 Rack Mount Screws 4 PD 415R SP PD 420R SP BRACKET MOUNTING Rack Mount Screws 4 Rack Mount Screws 4 Rack Mount Screws 2 Page 8 NOTE Any...

Page 9: ...ord and plug type connections to the PD HW15 SP are explicitly prohibited Ground conductor must be green with or without yellow stripe s and must be connected to earth ground at the service equipment...

Page 10: ...s only Lower Limit Cutoff Lower Limit Restore DETAILS SPECIFICATIONS 15 Amp RMS load 120 VAC 20 Amp RMS load 120 VAC 90 150V 5 watts 35 C 330V 186V for a nominal line voltage of 132V 1000 surges 6000...

Page 11: ...NTY IS IN LIEU OF ALL OTHER WARRANTIES OF ANY KIND EITHER EXPRESSED OR IMPLIED INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO THE MAXIMUM EX...