Page 7
GROUNDING AND BONDING (Continued)
Door Bonding Points
(1 Upper and 1 Lower)
NOTE:
The main protective earth conductor needs to be
the first terminal placed on the PET and this terminal
needs to be secured on its own with a nut.
1) Attach
Lower rear
door bonding wire
from
1/4”-20 protective earth terminal (PET)
to door bonding stud (10-32).
(FIGURE A)
-OR-
Attach
Upper rear
door bonding wire
from
upper bonding stud (10-32) to door bonding stud
(10-32).
(FIGURE B)
Door
2)
FOR OPTIONAL FRONT DOOR:
Attach
door bonding wire
(with male or female disconnect end) to door bonding
point with thread forming screw.
(FIGURE C)
3) Attach remaining door bonding wire to nearest bonding
stud (10-32).
(FIGURE C)
4) Connect male and female ends of door bonding
wire set.
Door Bonding Stud
(10-32)
Upper Bonding Stud (10-32)
PET Stud
(1/4”-20)
Lower Bonding Studs (10-32)
FIGURE A
FIGURE B
FIGURE C