Page 6
GROUNDING AND BONDING
Protective Earth Terminals (PET) are located on the bottom frame of the enclosure. These terminals are marked with
the symbol.
Enclosure accessory parts contain or are provided with bonding points for connection to the frame / PET.
Protective earth and bonding connections shall be in accordance with Article 250 of the National Electric Code.
When removing any bonded accessory for servicing the enclosure, make sure to disconnect the bonding terminal from the
accessory. NOTE: The bonding terminal MUST be reconnected to the accessory when the part is replaced after servicing.
(1)
(1)
OPTIONAL PROTECTIVE EARTH TERMINAL KIT: #PET-K-FD
PARTS LIST
• Door bonding wire [12 Gauge Wire
(#10 ring terminal to male disconnect) 6”]
• Door bonding wire [12 Gauge Wire
(#10 ring terminal to female disconnect) 4”]
• Thread forming screw M4 x .7
• Locking Nut 10-32
QTY
(1)
(1)
(1)
(1)
(1)
(1)
PARTS LIST
• Lower door bonding wire [12 Gauge Wire
(#10 ring terminal to #10 ring terminal) 14”]
• Lower door bonding wire [12 Gauge Wire
(#10 ring terminal to 1/4-20 ring terminal) 14”]
• Flange Nut 10-32
• Flange Nut 1/4-20
• Locking Nut 10-32
QTY
(1)
(1)
(2)
(1)
(1)
(1)
(1)
(2)
OPTIONAL PROTECTIVE EARTH TERMINAL KIT: #PET-K-RD
(1)
(1)