background image

8

Midco 

International

 Inc.

8470 23

 

 

Type of   

Ignitor Orifi ce  

Recommended   

  Ignitor

 

 

  Gas 

 

   Diameter    Ignitor Gas Pressure  

Gas Rate

 

 

NATURAL 

.052 (#55Dr.)  

3.5″ W.C. 

 

 

  6 MBH

 

 

PROPANE  .042 (#58Dr.)  

3.5″ W.C. 

 

 

  7 MBH

Proper operation of the fl ame sensor rod can be checked by measuring the fl ame current. With 

the Electronic Control energized, a good reading should run steady 2 or more microamps.

When servicing, clean the Ignitor Retention Plate ports and blow out the internal air and gas 

passages. Clean the Electrode Insulators and check them for hairline cracks. Also check the 
electrode ends and the Ground Barrier for serious corrosion or loss of metal. Replace any defective 
parts.

Make sure that there is no 

debris in the Blast Tube that could 
short out the Spark or Flame 
Electrode.

Clean the Ignitor Gas Orifi ce in 

Tee Orifi ce Fitting (see Figure 5) and 
check that the orifi ce size is correct 
per Table 3.

Check that the electrode ends 

are positioned and that the gap 
between the end of each electrode 
and the ground barrier is spaced per 
Figure 5.

Check that the Ignitor Air 

Defl ector is at the correct angle 
(45°). See Figure 4.

Inspect the electrode wire 

insulation for cracks or worn areas, 
or any contact with the burner frame. 
Dampness will facilitate electrical 
leakage to ground, which will cause 
ignition or fl ame signal failure.

SPARK TEST

—Main Manual 

Shut-Off  Valve must be off . Place the 
Ignitor Assembly on top of the burner 
with the electrode ends visible and 
good metal to metal contact between 
the Ignitor Mounting Plate and the 
burner chassis. 

Connect the high voltage wire 

to the spark electrode. Spark should be visible during 6-second trial for ignition period and arc from 
the electrode end to the Ground Barrier. It should be audible and visible, though it is rather thin and 
diffi  cult to see in bright light.
 

CAUTION: Circuit has 30,000 volt open circuit potential.

If the spark is not audible or visible it is leaking directly to ground. Before removing electrodes, 

check to make sure voltage is available by positioning the spark wire 1/8″ from the end of the 
electrode.

Disconnect Flame Electrode 

wire and switch the high voltage wire to the fl ame electrode and 

repeat test for insulator leakage.
 

CAUTION: Do not indiscriminately change the ignitor gas orifi ce size as ignition troubles 

are rarely cured in this manner. The ignitor utilizes a premixed gas/air mixture and, as the 
air input is relatively fi xed, any adjustment to the gas/air ratio that might be required for a 
specifi c application should be made by careful adjustment of the ignitor regulator to vary 
its outlet gas pressure. Pressure adjustments must be made when the gas is fl owing. If 
cleaning and electrode adjustment does not eliminate an ignition problem, further checks are 
required. Refer to Trouble Chart.

 

 

  

 

    __________________________________________

The valve is a single function on-off  type with automatic closing on current failure. Replace
entire valve if valve fails to open when power is applied or if leakage is defected on standby.
 

 

  

 

    __________________________________________

Table 3 1 - 

Ignitor Firing Rate

  VIII  Ignitor &

Regulator

Assembly

Continued

Figure 5 - 

Ignitor and Flame Sensor Assembly

IGNITOR 

SPIDER

SENSE 

ROD

.25

GROUND

BARRIER

SPARK ELECTRODE

POSITION ELECTRODES TO CENTER

HOLE ON RETENTION PLATE

IGNITOR 

GAS
PRESSURE 

IGNITOR REGULATOR

IGNITOR 

MOUNTING PLATE

INSULATOR

INSULATOR 

CLAMP

CLAMP SCREWS

 1/8 TO 5/32 GAP

 1/8 TO 5/32 GAP

IGNITOR GAS ORIFICE

(HIDDEN: SIDE TAP OF TEE)

TEE ORIFICE FITTING

IGNITOR 

GAS LINE

IGNITOR TIP

RETENTION PLATE

TEST TAP

IX  Main 

Automatic Valve

Service

Summary of Contents for Incinomite J83-DS

Page 1: ...his or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately phone your gas supplier fr...

Page 2: ...000 feet by 4 for each 1000 feet of additional elevation 4 100 MBH 100 000 BTU Hr 5 Kit is available for eld installation Specifications 1 Speci cations and Installation No 1 Waste Primarily dry mater...

Page 3: ...arometric damper of the same size as the vent connector should be installed If the chimney is high enough to make it di cult for the barometric to maintain a maximum incineration chamber over re draft...

Page 4: ...800 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 PROPANE PROPANE Gas 2 500 BTU Cu Ft with 3 8 Main Gas Port 8 0 9 0 10 0 11 0 Capacities shown are for total pressure drop of 0 3 W C For higher permissible press...

Page 5: ...based on the pressure available at the inlet to the supply pipe branch line when all other gas equipment fed by the same source NATURAL gas meter or PROPANE tank regulator is ring at full rate Also ta...

Page 6: ...ION Purge outside the building Do not purge into the incineration chamber 5 Turn on the Fused Disconnect Burner Switch or Timer Let motor run long enough to accomplish four air changes Note that motor...

Page 7: ...cineration chamber pressure stays within the range of 0 to minus 0 5 W C 16 WARNING When the incinerator is located inside a building and a draft control is used check that there is no spillage of ue...

Page 8: ...to the Ground Barrier It should be audible and visible though it is rather thin and di cult to see in bright light CAUTION Circuit has 30 000 volt open circuit potential If the spark is not audible o...

Page 9: ...against the side plate of the blower housing Testing the switch to prove that it is functional can be done by removing the ignitor assembly and blowing hot air through the opening toward the blower in...

Page 10: ...Valve terminal and strip terminal 10 No voltage Electronic Control or Fuse is defective 2 Check for 24 V between strip terminals 7 and 10 No voltage blue wire from strip terminal 7 is defective 3 Chec...

Page 11: ...t 2 microamps Check sense wire for continuity Adjust ignitor gas pressure to obtain acceptable signal and note gas pressure and signal strength for future reference A Low gas pressure B Air shutter op...

Page 12: ...oria Street Chicago Illinois 60646 toll free 866 705 0514 tel 773 604 8700 fax 866 580 8700 web www midcointernational com e mail sales midcointernational com 12 Printed in USA 8470 23 ISO 9001 C O MP...

Reviews: