background image

Midco International Inc.

7

8470 23

 

11. Reset the Blower Air Shutter to match the intended input, i.e.; full open for maximum, closed 

 

for minimum or partially open for midrange. The Blower Air Shutter is factory set wide open. 

 

Adjust as necessary when, with combustion air available in the incineration chamber, it is    

 

 

desirable to increase the fl ame length, or to restrict the amount of excess air discharged into the  

 

incineration chamber when the burner input is below 450 MBH.

 

12. The actual NATURAL gas fi ring rate in BTU per hour can be determined by timing the gas 

 

meter. Accurately time the meter test dial for one revolution, convert to hourly cubic feet and    

 

multiply by the BTU per cubic foot value of your gas per formula:

 

 

 

 

 

3600 x test dial size x BTU value       

= BTU/Hr.

 

 

 

 

     No. of seconds for one rev. test dial

 

Then divide by 1,000 for MBH value.

 

 

 

Example: 3600 x 1 x 1000*  = 360,000 BTU/HR = 360 MBH 

 

 

 

 

 

 

    10

 

*Approximate BTU value

 

13. Start and stop the burner several times to check its operation with the charging door open,   

 

and then with it closed. Remove any temporary Door Open bypasses installed in Step 6.

 

14. Test operation of any auxiliary operating and/or limit controls.

 

15. Load incinerator and make trial run. Confi rm that the incineration chamber pressure stays    

 

within the range of 0 to minus 0.5″ W.C.

 

16.   

WARNING: When the incinerator is located inside a building and a draft control   

 

is used, check that there is no spillage of fl ue products from the draft control.

 

17. To shut off : Turn Burner Switch or Timer off  and close Main Manual Shut -Off  Valve 

 

 

 

WARNING: BE SURE THAT THE MANUAL VALVE AND BURNER DISCONNECT    

 

 

SWITCH ARE TURNED OFF BEFORE ANY PARTS ARE REMOVED FOR SERVICE. 

 

 

  

 

    __________________________________________

The Ignitor and Regulator Assembly is removed as a unit. Disconnect the ignitor gas line and 
electrode wires, remove the two mounting screws and pull out the assembly.

When the ignitor gas pressure is in the proper range (see Table 3) and the electrodes are 

adjusted to the dimensions shown in Figure 5, any ignition problems are usually caused by lint, dust, 
corrosion, cracked electrode insulators, foreign matter in the blast tube or deterioration of ignitor 
ports in Retention Plate.

Ignitor trouble will be evidenced by failure of main burner ignition. It may cause frequent 

Electronic Control lockout. Check for dirt in the ignitor air and mixture passageways and check for 
obstructions in the ignitor ports. Also check electrode adjustments (see Figure 5). Replace any 
severely burned parts. 

Initial Start Up /
Adjustment
Continued

Service

VIII  Ignitor &
Regulator 
Assembly

Figure 4 - 

General Burner Head Assembly

Installation and Service

Summary of Contents for Incinomite J83-DS

Page 1: ...his or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately phone your gas supplier fr...

Page 2: ...000 feet by 4 for each 1000 feet of additional elevation 4 100 MBH 100 000 BTU Hr 5 Kit is available for eld installation Specifications 1 Speci cations and Installation No 1 Waste Primarily dry mater...

Page 3: ...arometric damper of the same size as the vent connector should be installed If the chimney is high enough to make it di cult for the barometric to maintain a maximum incineration chamber over re draft...

Page 4: ...800 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 PROPANE PROPANE Gas 2 500 BTU Cu Ft with 3 8 Main Gas Port 8 0 9 0 10 0 11 0 Capacities shown are for total pressure drop of 0 3 W C For higher permissible press...

Page 5: ...based on the pressure available at the inlet to the supply pipe branch line when all other gas equipment fed by the same source NATURAL gas meter or PROPANE tank regulator is ring at full rate Also ta...

Page 6: ...ION Purge outside the building Do not purge into the incineration chamber 5 Turn on the Fused Disconnect Burner Switch or Timer Let motor run long enough to accomplish four air changes Note that motor...

Page 7: ...cineration chamber pressure stays within the range of 0 to minus 0 5 W C 16 WARNING When the incinerator is located inside a building and a draft control is used check that there is no spillage of ue...

Page 8: ...to the Ground Barrier It should be audible and visible though it is rather thin and di cult to see in bright light CAUTION Circuit has 30 000 volt open circuit potential If the spark is not audible o...

Page 9: ...against the side plate of the blower housing Testing the switch to prove that it is functional can be done by removing the ignitor assembly and blowing hot air through the opening toward the blower in...

Page 10: ...Valve terminal and strip terminal 10 No voltage Electronic Control or Fuse is defective 2 Check for 24 V between strip terminals 7 and 10 No voltage blue wire from strip terminal 7 is defective 3 Chec...

Page 11: ...t 2 microamps Check sense wire for continuity Adjust ignitor gas pressure to obtain acceptable signal and note gas pressure and signal strength for future reference A Low gas pressure B Air shutter op...

Page 12: ...oria Street Chicago Illinois 60646 toll free 866 705 0514 tel 773 604 8700 fax 866 580 8700 web www midcointernational com e mail sales midcointernational com 12 Printed in USA 8470 23 ISO 9001 C O MP...

Reviews: