Midco Economite 400B-02 Series Installation And Service Instructions Manual Download Page 4

The Vent Connector shall be installed so as to avoid turns or other construction features

which create excessive resistance to flow of vent gas. It shall be installed without any dips sags

and shall slope upward at least 1/4" per
foot.

A manually operated damper shall

not

be placed in the Vent Connector or

chimney of any gas utilization equipment.

The Vent Connector shall be firmly

attached to draft hood outlets and flue
collars. Joints between sections of con-
nector piping shall be fastened by sheet-
metal screws or other approved means.
The Vent Connector shall be supported
for the design and weight of the material
employed to maintain clearance and pre-
vent physical damage and separation of
joints.

Gas utilization equipment requiring

controlled draft may be equipped with a
listed double acting barometric draft reg-
ulator, 

if approved by local codes.

It

must be installed and adjusted in accor-
dance with the manufacturer's instruc-
tions.

A draft hood or a barometric draft

regulator shall be installed in the same
room or enclosure as the equipment in
such a manner as to prevent any differ-
ence in the pressure between the hood
or regulator and the combustion air sup-
ply. In no case shall the relief opening of
the draft hood or barometric draft regula-
tor be located at a point lower than the
top of the highest flue passage in the
equipment.

A device which will automatically

shut off gas to the burner in the event of
sustained backdraft is recommended if
such backdraft might adversely affect
burner operation or if flue gas spillage
might introduce a hazard. If such a

device is used, it shall be of the listed
type and installed and adjusted by a qual-
ified service technician in accordance
with the manufacturer's instructions.

Installation wiring and grounding of the burner must conform to local codes, or in their absence
in the 

United States to National Electric code, ANSI/NFPA No. 70-latest edition; in Canada,

to Canadian Electrical Code Part 1, CSA Standard C22.1.

Use copper wire not less than 14 gauge for line voltage wiring. Hook up to a dedicated line

with an on-off disconnect switch and a minimum 10 amp breaker.

The frame of the burner should be well grounded. Normally the piping and/or electric con-

duit will provide sufficient grounding. However, a terminal is provided on the terminal strip for
positive grounding where insulated pipe couplings are used or where any doubt exists regard-
ing grounding sufficiency.

Confirm that the polarity is correct—hot wire strip terminal 

1

, neutral 

2

— and that the neu-

tral line is not subject to induced low voltage (check 

2

to earth ground) from other equipment.

Each installation must include suitable limit controls. Existing oil burner combination limit

and operating controls are normally 

NOT SUITABLE

for gas burner use.

Set the thermostat heat anticipator for the total current draw handled by the thermostat.

The current draw of the ECONOMITE 24V operating circuit is 0.3 amps on 400B-02 (NATUR-
AL) and 0.7 amps on 400B-02P (PROPANE).

4

IV Vent Connector 

Continued

V Electrical

Figure 3: Draft Hoods

Figure 4: Barometric Dampers

Figures 3 and 4: Copyright by the 

American Gas Association. Used by 

permission of the copyright holder.

Summary of Contents for Economite 400B-02 Series

Page 1: ...tion equipment and remove such hazards Affix this manual adjacent to the conversion burner CODE COMPLIANCE IS THE SOLE RESPONSIBILITY OF THE INSTALLER WARNING If the information in these instructions...

Page 2: ...g provision must be made for an outside air supply near the gas utilization equipment area Install permanently open grilles sized at not less than one square inch free area per 4 000 BTU of burner inp...

Page 3: ...NG Burner cabinet must be mounted in orientation shown in figures 1 and 2 Any other mountings may cause a dangerous condition and will void burner warranty and agency approvals Non standard arrangemen...

Page 4: ...rsely affect burner operation or if flue gas spillage might introduce a hazard If such a device is used it shall be of the listed type and installed and adjusted by a qual ified service technician in...

Page 5: ...of 5 0 W C pressure 11 0 W C PROPANE to the inlet of the Combination Valve when the burner and all other gas utilization equipment are on Note If there is more than 1 0 W C differential in the inlet p...

Page 6: ...and install the spud with the correct orifice size stamped with inch diameter from the SPUD KIT bag If the required firing rate is at the minimum of a capacity range select the next lower range spud...

Page 7: ...ustment 8 Turn operating control to ON or set thermostat above room temperature Main flame should come on when the motor reaches operating speed If not refer to Trouble Chart To make a preliminary set...

Page 8: ...C for NATUR AL gas 8 0 W C for PROPANE 1 Standby gas pressure inches W C 2 The efficiency of the thermocouple and the pilotstat safety control can be determined by timing the safety shut off With the...

Page 9: ...te and electrical interlock switch so as to prevent the burner from firing if the Blower Wheel is not running at its operat ing speed When the motor is off the actuator spring forces the disk against...

Page 10: ...u 5 for the method of isolating the problem If on a call for heat the main burner fails to operate even though the pilot is burning and the motor is running failure of the electric valve operator s ma...

Page 11: ...t flame gas pressure See Section IX Venturi Casting and Pilot E Clogged pilot orifice s See Section IX Venturi Casting and Pilot F Defective ignitor ignitor wires spark rod or improper spark gap See F...

Page 12: ...ent closed too far D Dirty Blower Wheel A Electric Valve Operator s of Combination Valve is defective and entire valve must be replaced Normal low voltage Motor running 24V minimum Combination Valve e...

Reviews: