background image

Notes:

*

Model 400B-02P is equipped with a 4-Function Redundant Main Automatic Valve.

**

SCFM=Standard Cubic Feet/Minute

***

Ratings based on 1,000 BTU/cu. ft. NATURAL, 2,500 BTU/cu. ft. PROPANE at Sea

Level.
****

1 MBH=1,000 BTU/Hr.

One gallon of fuel oil=140,000 BTU.
Derate burner for altitudes over 2,000 feet by 4% for each 1,000 feet above sea level.

CAUTION: The ECONOMITE 400B-02(P) is not intended for outdoor installa-

tion and must be protected from excessive moisture. Provide adequate clear-
ance for service and proper operation.

If the former automatic oil burner gave trouble-free operation, it is probable that the gas utiliza-
tion equipment area has sufficient infiltration of air for combustion and dilution of flue gases.

Nevertheless, the area must be checked:

Open basement or utility areas of normal construction, without storm windows or tight doors,

will generally allow sufficient air infiltration. However, if the gas utilization equipment is located
in a tight or separate room, ventilation to an open area as described above will be required.
Install two permanently open grilles, each sized on the basis of one square inch free area per
1,000 BTU (but not less than 100 square inches) of the total input rating of all gas utilization
equipment in the combined space. One grille should be located within 12 inches of the ceiling,
the other within 12 inches of the floor.

If the gas utilization equipment is located in an area of unusually tight construction, or if an

exhaust fan, kitchen ventilation system, clothes dryer and/or fireplace is installed in the build-
ing, provision must be made for an outside air supply near the gas utilization equipment area.
Install permanently open grilles sized at not less than one square inch free area per 4,000 BTU
of burner input. When ventilating through horizontal ducts, grilles should be sized at not less
than one square inch free area per 2,000 BTU of burner input. In any case, the minimum
dimension of rectangular air ducts shall not be less than 3 inches.

In Canada, for detailed ventilation requirements, refer to standard CAN/CGA 1-B149.1 or .2

and/or local codes.

Clean the gas utilization equipment, heat exchanger interior, combustion chamber, and flue

connections. Remove all adhering tars, scale, dirt and soot. Inspect for actual leaks and/or
potential leaks.

Cement all joints, including those in the gas utilization equipment base and around door

frames, to prevent leakage into or out of the combustion chamber.

The access or firing door should open easily to relieve pressure. If positive latches exist,

they should be modified to permit easy opening; a spring loaded door holder is recommended.

On all boilers, make certain the pressure relief safety valve is in good operating condition.

Specifications

2

Model 400B-02 NATURAL Gas only

Model 400B-02P PROPANE Gas*

Air Delivery 

(Approximate air delivery at zero draft)

Maximum Firing Rate***

Minimum Firing Rate***

Tube Diameter

Tube Length

Minimum Combustion Chamber Size

400 MBH

300 MBH

200 MBH

Gas Pressure Required

NATURAL

PROPANE

Standard Voltage

Pilot Safety

85 SCFM**

400 MBH****

200 MBH****

4 inches

9 inches

10" W x 16

1

/

2

L or 15" dia.

9" W x 14" L or 13" dia.

7" W x 11" L or 10" dia.

5.0" to 14.0" W.C.

11.0" to 14.0" W.C.

120 Volts   60 Cycle

Thermoelectric, 100% shut-off

I Ventilation

II Preparation of the Gas

Utilization Equipment

Part 1 Installation

Summary of Contents for Economite 400B-02 Series

Page 1: ...tion equipment and remove such hazards Affix this manual adjacent to the conversion burner CODE COMPLIANCE IS THE SOLE RESPONSIBILITY OF THE INSTALLER WARNING If the information in these instructions...

Page 2: ...g provision must be made for an outside air supply near the gas utilization equipment area Install permanently open grilles sized at not less than one square inch free area per 4 000 BTU of burner inp...

Page 3: ...NG Burner cabinet must be mounted in orientation shown in figures 1 and 2 Any other mountings may cause a dangerous condition and will void burner warranty and agency approvals Non standard arrangemen...

Page 4: ...rsely affect burner operation or if flue gas spillage might introduce a hazard If such a device is used it shall be of the listed type and installed and adjusted by a qual ified service technician in...

Page 5: ...of 5 0 W C pressure 11 0 W C PROPANE to the inlet of the Combination Valve when the burner and all other gas utilization equipment are on Note If there is more than 1 0 W C differential in the inlet p...

Page 6: ...and install the spud with the correct orifice size stamped with inch diameter from the SPUD KIT bag If the required firing rate is at the minimum of a capacity range select the next lower range spud...

Page 7: ...ustment 8 Turn operating control to ON or set thermostat above room temperature Main flame should come on when the motor reaches operating speed If not refer to Trouble Chart To make a preliminary set...

Page 8: ...C for NATUR AL gas 8 0 W C for PROPANE 1 Standby gas pressure inches W C 2 The efficiency of the thermocouple and the pilotstat safety control can be determined by timing the safety shut off With the...

Page 9: ...te and electrical interlock switch so as to prevent the burner from firing if the Blower Wheel is not running at its operat ing speed When the motor is off the actuator spring forces the disk against...

Page 10: ...u 5 for the method of isolating the problem If on a call for heat the main burner fails to operate even though the pilot is burning and the motor is running failure of the electric valve operator s ma...

Page 11: ...t flame gas pressure See Section IX Venturi Casting and Pilot E Clogged pilot orifice s See Section IX Venturi Casting and Pilot F Defective ignitor ignitor wires spark rod or improper spark gap See F...

Page 12: ...ent closed too far D Dirty Blower Wheel A Electric Valve Operator s of Combination Valve is defective and entire valve must be replaced Normal low voltage Motor running 24V minimum Combination Valve e...

Reviews: