background image

A combustion chamber liner is normally required to protect non-heat transfer surfaces and to
provide a radiant bed for rapid heat transfer to the primary surfaces of the heat exchanger. In

most cases, the oil burner combustion chamber
liner formerly used can be used, if in good condi-
tion.

In the case of wet base boilers, where the

entire combustion chamber is comprised of heat
exchange surfaces and no combustion chamber
liner was provided for oil firing, a liner is usually
not required for the ECONOMITE. However, a
liner or target wall may be necessary if the com-
bustion chamber is unusually short, in order to
avoid flame contact on the heat exchanger walls
or flueways.

If a built up chamber liner is required, use

2300°F minimum insulating material.

The burner tube, or the stainless steel sleeve

that is included with the burner, must be sealed
air tight into the combustion chamber liner open-
ing with refractory material as shown by Figures

1,2 and 7. The sleeve is preferred as it is

designed to properly locate the end of the tube relative to the inside wall of the combustion
chamber, and to permit burner removal without breaking the seal.

CAUTION:

In no case should the burner tube be allowed to extend into the cham-

ber proper; it must be set at least 1" short of the inside surface , because high combus-
tion chamber temperatures will cause premature thermocouple and pilot deterioration.

Special heat resistant alloy extension tubes and instructions are available for those applica-

tions where the burner tube is too short to reach the combustion chamber (such as old-fash-
ioned gravity warm air furnace installations).

WARNING: Burner cabinet must be

mounted in orientation shown in figures 1
and 2. Any other mountings may cause a
dangerous condition, and will void burner
warranty and agency approvals. Non-
standard arrangements may be available
for some models; consult factory for
details if required.

Before permanently setting the burner in place,

check venturi casting openings and pilot assem-
bly to make sure they are free of foreign materi-
als. See Figure 8.

WARNING: The chimney shall be

inspected for unsafe conditions such as

deteriorated masonry and excessive soot

or other blockage or potential blockage.. Installation must conform with local
codes or in the absence of local codes with ANSI Z21.8 latest edition and NFPA,
ANSI Z223.1 latest edition.

WARNING: The Vent Connector shall not be con-

nected to a chimney already venting solid fuel burning
appliances, an incinerator or an open fireplace.

The Vent Connector shall be made of non-combustible, corro-

sion resistant material capable of withstanding the vent gas tem-

perature produced by the gas utilization equipment and of suffi-
cient thickness to withstand physical damage.

 

 

 

 

The Vent Connector shall be as short as possible.  The

entire length shall be readily accessible for inspection, cleaning and replacement.

The length of horizontal uninsulated Vent Connector between chimney and a single gas uti-

lization equipment shall not exceed 75% of the height of the chimney above the connector, or
100% if the Vent Connector is insulated.

3

III Combustion Chamber

IV Chimney, Vent

Connector*, 

and Draft Control

*Formerly referred to as Flue Pipe

Figure 1:

Dry Base Boiler with Combustion

Chamber Liner (Warm Air Furnace

Construction is Similar)

Figure 2:

Wet Base Boiler with 

Combustion Chamber Unlined

Maximum

Firing Rate

Vent 

Connector

250 MBH

320 MBH

400 MBH

7"

8"

9"

Table 1: Recommended

Vent Connector Sizes

Summary of Contents for Economite 400B-02 Series

Page 1: ...tion equipment and remove such hazards Affix this manual adjacent to the conversion burner CODE COMPLIANCE IS THE SOLE RESPONSIBILITY OF THE INSTALLER WARNING If the information in these instructions...

Page 2: ...g provision must be made for an outside air supply near the gas utilization equipment area Install permanently open grilles sized at not less than one square inch free area per 4 000 BTU of burner inp...

Page 3: ...NG Burner cabinet must be mounted in orientation shown in figures 1 and 2 Any other mountings may cause a dangerous condition and will void burner warranty and agency approvals Non standard arrangemen...

Page 4: ...rsely affect burner operation or if flue gas spillage might introduce a hazard If such a device is used it shall be of the listed type and installed and adjusted by a qual ified service technician in...

Page 5: ...of 5 0 W C pressure 11 0 W C PROPANE to the inlet of the Combination Valve when the burner and all other gas utilization equipment are on Note If there is more than 1 0 W C differential in the inlet p...

Page 6: ...and install the spud with the correct orifice size stamped with inch diameter from the SPUD KIT bag If the required firing rate is at the minimum of a capacity range select the next lower range spud...

Page 7: ...ustment 8 Turn operating control to ON or set thermostat above room temperature Main flame should come on when the motor reaches operating speed If not refer to Trouble Chart To make a preliminary set...

Page 8: ...C for NATUR AL gas 8 0 W C for PROPANE 1 Standby gas pressure inches W C 2 The efficiency of the thermocouple and the pilotstat safety control can be determined by timing the safety shut off With the...

Page 9: ...te and electrical interlock switch so as to prevent the burner from firing if the Blower Wheel is not running at its operat ing speed When the motor is off the actuator spring forces the disk against...

Page 10: ...u 5 for the method of isolating the problem If on a call for heat the main burner fails to operate even though the pilot is burning and the motor is running failure of the electric valve operator s ma...

Page 11: ...t flame gas pressure See Section IX Venturi Casting and Pilot E Clogged pilot orifice s See Section IX Venturi Casting and Pilot F Defective ignitor ignitor wires spark rod or improper spark gap See F...

Page 12: ...ent closed too far D Dirty Blower Wheel A Electric Valve Operator s of Combination Valve is defective and entire valve must be replaced Normal low voltage Motor running 24V minimum Combination Valve e...

Reviews: